LC1F1250MD

Schneider Electric

Contactor,TeSys F,3P(3NO), AC-1, <=690V 1260 A, coil 220V DC

AVAILABLE

GET A QUOTE NOW

  • "TeSys F contactor, 3 poles (3NO), 1250A/690V AC-1, for non-inductive load applications. It provides a low sealed consumption 220/230V DC coil, bolt terminals for bars or cables with lugs. For high operating rates until 600 cycles/hour and environments until 55\u00b0C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC), Green Premium compliant (RoHS/REACh)."
Read more arrow Read less arrow
Specification Value
Product Certifications CB || UL || CSA || CQC || CE || UKCA || CCC
Power Dissipation Per Pole 120 W AC-1
Average Impedance 0.12 mOhm - Ith 1260 A 50 Hz
[Ith] Conventional Free Air Thermal Current 1260 A (at 40 °C)
Control Circuit Voltage Limits operational 0.85...1.1 Uc 55 °C) || drop-out 0.2...0.35 Uc 55 °C)
Standards EN 60947-1 || IEC 60947-1 || JIS C8201-4-1 || EN 60947-4-1 || IEC 60947-4-1
Mounting Support plate
Control Circuit Type DC standard
Hold-In Power Consumption In W 9-9 W 20 °C
Rated Breaking Capacity 1890 A conforming to IEC 60947-4-1
Associated Fuse Rating 1000 A gG at <= 440 V
[Uimp] Rated Impulse Withstand Voltage 8 kV
Connections - Terminals control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 100 x 5 mm || power circuit bolted connection
Pole Contact Composition 3 NO
Operating Time 60...70 ms closing || 40...50 ms opening
Maximum Operating Rate 1200 cyc/h 55 °C
Tightening Torque control circuit 1.2 N.m || power circuit 58 N.m
Inrush Power In W 1600-1600 W 20 °C)
Compatibility Code LC1F
Overvoltage Category III
[Ui] Rated Insulation Voltage 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current 3000 A 40 °C - 3 min || 8000 A 40 °C - 10 s || 5200 A 40 °C - 30 s || 4000 A 40 °C - 1 min || 2000 A 40 °C - 10 min
Heat Dissipation 9-9 W
[Uc] Control Circuit Voltage 230 V DC
Range Of Product TeSys F
[Ue] Rated Operational Voltage <= 460 V DC || <= 690 V AC 50/60 Hz
Contactor Application resistive load
Product Or Component Type contactor
Range TeSys
Utilisation Category AC-1
[Ie] Rated Operational Current 1260 A (at <40 °C) AC-1
Poles Description 3P
Device Short Name LC1F
Read more arrow Read less arrow
*New items come with up to 24 month Obso Warranty
Our previously used items and repair options come with 12 months Obso Warranty.


"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
*Same & Next Day Delivery & Collection is available for stock from our UK and NL branches. Next-day delivery collection and 2 day delivery is available for stock sourced from our partners. In 90% of cases, we can deliver faster than the manufacturer’s ETA where required.

Standard options for delivery are also available where required.


"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
We are ISO 9001 accredited so you have peace of mind with your purchase.

What our customers say about us

Trustpilot

1

Step 1

    Part added for enquiry

    2

    Step 2

    Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.

    3

    Step 3

    We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.

    4

    Step 4

    Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.