EMS59201
Schneider Electric
PowerLogic SC150 CT-LPVT/VT: Switch controller, 1/5 A, LPVT/VT sensors
AVAILABLE
GET A QUOTE NOW
- "The Easergy SC150 module offers many high-performance features needed to measure and detect a fault current on the MV line. The switch controller are designed for clip in DIN rail. The measurement voltage range from 0\u202610 VAC LPVT and from 47\u2026240 VAC VTs. It include 8 digital inputs, 2 digital relay switch, and 2 RJ45 communication port. The operating temperature is -40\u00b0C to + 70\u00b0C. The storage temperature is -40\u00b0C to + 85\u00b0C. Mechanical dimensions are 140 mm in height, 45 mm in width and 140 mm in depth."
| Specification | Value |
|---|---|
| Range Of Product | PowerLogic T300 |
| Device Short Name | SC150 |
| Communication Port Support | 2 ETHERNET RJ45 |
| Measurement Voltage | : 0-10 V LPVT AC at 50/60 Hz (single or three phases) || : 47-240 V VTs AC at 50/60 Hz (single or three phases) |
| Number Of Outputs | 2 digital (relay) switch: |
| Continuous Output Current | 8 A |
| Memory Capacity | 4 MB |
| Output Voltage | 12...127 V DC motor: || 90...220 V AC motor: |
| Protection Type | ANSI 50/51 : overcurrent || ANSI 50N/51N : earth fault || ANSI 67 : directional phase overcurrent || ANSI 67N : directional earth fault || ANSI 47 : negative sequence overvoltage || ANSI 27 : undervoltage || ANSI 59 : overvoltage || ANSI 59N : neutral voltage displacement || ANSI 37 : phase undercurrent |
| Type Of Measurement | apparent power || voltage || active and reactive power || active and reactive energy || power factor || current || frequency || apparent energy |
| Product Or Component Type | MV switch controller |
| Irms Rated Making Capacity | 15 A 4 s |
| Measurement Current | 5-5 A || 1-1 A |
| Maximum Switching Voltage | 440 V AC |
| Number Of Inputs | 8 digital IEC 61131-2 type 3 |
| [Us] Rated Supply Voltage | 12...48 V DC +/- 20 % |
| Communication Port Protocol | IEC 60870-5-104 |
| Power Consumption In Va | 2 VA |
| Software Function | assistance in commissioning and operating the installation || security/authority verification || alarm || event log || Operating/Status report || reports and diagrams |
| Control Type | illuminated push-button status: |
| Data Recording | sag and swell logs || harmonics logs || min/max of instantaneous values || demand values || event logs || sequence of event recording || counter || current value before fault |
| Breaking Capacity | 2000 VA |
| Analogue Input Type | current 0.01...35 A (impedance 0.001 Ohm)4 x |
| Type Of Measurement | current class 0.5 || voltage class 0.5 || energy class 1 IEC 61557-12 |
| Synchronisation Time Between Inputs | 1 ms |
| Power Quality Analysis | voltage unbalance || individual harmonics || voltage sag and swell detection || harmonic distortion || voltage magnitude |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews





