LTMR100DBD

Motor controller, TeSys T, Motor Management, DeviceNet, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 24VDC

Dostępny

Uzyskaj wycenę już teraz

-

Specification Value
Contacts Type And Composition 1 NO + 1 NC fault signal || 3 NO
Height 61 mm
Connection Pitch 5.08 mm
Permissible Power 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Network And Machine Diagnosis Type running hours counter/operating time || starting current and time || trip context information || remaining operating time before overload tripping || fault recording || phase fault and earth fault trip counters || event recording || trip history information || waiting time after overload tripping || motor control command recording
Pollution Degree 3
Logic Input Number 6
Maximum Operating Rate 1800 cyc/h
Connections - Terminals control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)solid without cable end
Input Current 7 mA
Current State 1 Guaranteed logic input < 15 V 2...15 mA 15 ms
Net Weight 0.53 kg
[Uimp] Rated Impulse Withstand Voltage 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1 || 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
Associated Fuse Rating 4 A gG output || 0.5 A gG control circuit
Electromagnetic Compatibility electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Measurement Accuracy 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 5 % active and reactive power || 0,02 current
Current State 0 Guaranteed logic input < 5 V <= 15 mA 5 ms
[Ui] Rated Insulation Voltage 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
Short-Circuit Withstand 100 kA conforming to EN/IEC 60947-4-1
Compatibility Code LTMR
Protection Type earth-leakage protection || overload || reverse polarity protection || thermal protection || overload (long time) || load fluctuation || phase failure || thermal overload protection || power factor variation || locked rotor || phase unbalance
Web Services web server
Width 91 mm
Load Current 5 A 250 V AC logic output || 5 A 30 V DC logic output
Tightening Torque control circuit 0.5-0.6 N.m flat 3 mm
Overvoltage Category III
Depth 122.5 mm
Maximum Operating Frequency 2 Hz
Metering Type temperature || average current Iavg || imbalance current || earth-fault current || phase current I1, I2, I3 RMS
Product Or Component Type motor controller
Product Name TeSys T
Measurement Current 5-100 A
Range TeSys
Current Consumption 56...127 mA
[Us] Rated Supply Voltage 24 V DC
Communication Port Protocol DeviceNet
Bus Type DeviceNet ISO 1198 1...64 125...500 kbit/s, terminal block 4 twisted shielded pairs cable
Supply Voltage Limits 20.4-26.24 V DC
Device Application equipment monitoring and control
Device Short Name LTMR
Więcej informacji arrow Czytaj mniej arrow
*Nowe produkty są objęte 24-miesięczną gwarancją Obso.
Nasze wcześniej używane produkty i opcje naprawy są objęte 12-miesięczną gwarancją Obso.


„Super obsługa! Wszystko zostało przetworzone bardzo szybko i kompetentnie, a osobiste wsparcie było doskonałe. Zawsze ponownie wybrałbym Obso Automation! Wielkie dzięki za świetne wsparcie.” - MJ
*Dostawa i odbiór tego samego i następnego dnia są dostępne dla towarów z naszych oddziałów w Wielkiej Brytanii i Holandii. Odbiór następnego dnia i dostawa w ciągu 2 dni są dostępne dla towarów pochodzących od naszych partnerów. W 90% przypadków możemy dostarczyć towar szybciej niż przewidywany czas dostawy producenta.

W razie potrzeby dostępne są również standardowe opcje dostawy.


„Profesjonalny, uprzejmy i dokładny. Przestarzała część wyceniona tego samego dnia i dostarczona następnego” - PT
Posiadamy akredytację ISO 9001, dzięki czemu możesz być spokojny o swój zakup.

Co mówią o nas nasi klienci

Trustpilot

1

Step 1

    Część dodana do zapytania

    2

    Krok 2

    Twój osobisty opiekun klienta już się tym zajmuje, zapewniając szybką reakcję i bezkonkurencyjną obsługę.

    3

    Krok 3

    Nie tylko przetwarzamy zamówienia – gwarantujemy sprawną dostawę, pełną przejrzystość i zero bólu głowy.

    4

    Krok 4

    Nie bez powodu zaufało nam ponad 10 000 klientów. Uzyskaj wycenę już teraz i doświadcz automatyzacji bez ryzyka, opóźnień i niepewności.