LC1F115

Contactor body,TeSys F,3P(3NO), AC-3, <=440V 115A, without coil

Dostępny

Uzyskaj wycenę już teraz

TeSys F contactor, 3 poles (3NO), 115A/690V AC-3, for motor applications up to 55kW@400V. Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Więcej informacji arrow Czytaj mniej arrow
Specification Value
Product Certifications RINA || ABS || CSA || DNV || RMRoS || BV || LROS (Lloyds register of shipping) || UL || CB || UKCA
Power Dissipation Per Pole 15 W AC-1 || 5 W AC-3
Average Impedance 0.37 mOhm - Ith 200 A 50 Hz
Control Circuit Voltage Limits operational: 0.85...1.1 Uc AC 40...400 Hz with LX9 coil || drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX9 coil || operational: 0.85...1.1 Uc DC with LX4 coil || drop-out: 0.15...0.2 Uc DC with LX4 coil || operational: 85...275 V AC 50/60 Hz with LXE coil || drop-out: 0...60 V AC 50/60 Hz with LXE coil || operational: 85...418 V DC with LXE coil || drop-out: 0...45 V DC with LXE coil
[Ith] Conventional Free Air Thermal Current 200 A (at 40 °C)
Standards EN 60947-1 || JIS C8201-4-1 || IEC 60947-4-1 || EN 60947-4-1 || IEC 60947-1
[Uc] Control Circuit Voltage 24...575 V AC 40...400 Hz with LX9 coil || 24...460 V DC with LX4 coil || 100...250 V AC 50/60 Hz with LXE coil || 100...380 V DC with LXE coil
Mounting Support plate
Rated Breaking Capacity 920 A conforming to IEC 60947-4-1
Irms Rated Making Capacity 1150 A conforming to IEC 60947-4-1
Associated Fuse Rating 125 A aM at <= 440 V || 200 A gG at <= 440 V
[Uimp] Rated Impulse Withstand Voltage 8 kV
Connections - Terminals power circuit lugs-ring terminals 1 95-95 mm² || power circuit connector 1 95-95 mm² || power circuit bar 2 20 x 3 mm || power circuit bolted connection || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²solid without cable end || control circuit screw clamp terminals 1 1-4 mm² || control circuit screw clamp terminals 2 1-4 mm² || control circuit screw clamp terminals 1.0 0.2-2.5 mm²flexible without cable end || control circuit screw clamp terminals 1.0 0.25-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1.0 0.2-2.5 mm²solid without cable end
Inrush Power In Va 590-855 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil || 543-665 VA (at 20 °C)with LX4 coil || 280-310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil || 270-320 VA (at 20 °C)with LXE coil
Maximum Operating Rate 2400 cyc/h 55 °C
Operating Time 35 ms closing with LX9 coil || 130 ms opening with LX9 coil || 30...40 ms closing with LX4 coil || 30...50 ms opening with LX4 coil || 40...80 ms closing with LXE coil || 6...54 ms opening with LXE coil
Tightening Torque power circuit 10 N.m || control circuit 1.2 N.m || control circuit 0.6 N.m
Mechanical Durability 10 Mcycles
Compatibility Code LC1F
Hold-In Power Consumption In Va 6.6-8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil || 3.94-4.83 VA (at 20 °C)with LX4 coil || 4.5-7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil || 2.5-4.0 VA (at 20 °C)with LXE coil
Overvoltage Category III
[Ui] Rated Insulation Voltage 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current 1100 A 40 °C - 10 s || 640 A 40 °C - 30 s || 520 A 40 °C - 1 min || 400 A 40 °C - 3 min || 320 A 40 °C - 10 min
Heat Dissipation 5.9-7.2 W || 2.2-5.5 W
[Ue] Rated Operational Voltage <= 690 V AC 50/60 Hz || <= 460 V DC
Contactor Application resistive load || motor control
Product Or Component Type contactor
Product Name TeSys F
Range TeSys
Pole Contact Composition 3 NO
[Ie] Rated Operational Current 200 A 40 °C) <= 440 V AC-1 || 115 A 55 °C) <= 440 V AC-3
Utilisation Category AC-1 || AC-4 || AC-3
Poles Description 3P
Motor Power Kw 55 kW at 380...400 V AC 50/60 Hz (AC-3) || 59 kW at 415 V AC 50/60 Hz (AC-3) || 59 kW at 440 V AC 50/60 Hz (AC-3) || 75 kW at 500 V AC 50/60 Hz (AC-3) || 30 kW at 220...240 V AC 50/60 Hz (AC-3) || 80 kW at 660...690 V AC 50/60 Hz (AC-3) || 18.5 kW at 400 V AC 50/60 Hz (AC-4)
Device Short Name LC1F
Więcej informacji arrow Czytaj mniej arrow
*Nowe produkty są objęte 24-miesięczną gwarancją Obso.
Nasze wcześniej używane produkty i opcje naprawy są objęte 12-miesięczną gwarancją Obso.


„Super obsługa! Wszystko zostało przetworzone bardzo szybko i kompetentnie, a osobiste wsparcie było doskonałe. Zawsze ponownie wybrałbym Obso Automation! Wielkie dzięki za świetne wsparcie.” - MJ
*Dostawa i odbiór tego samego i następnego dnia są dostępne dla towarów z naszych oddziałów w Wielkiej Brytanii i Holandii. Odbiór następnego dnia i dostawa w ciągu 2 dni są dostępne dla towarów pochodzących od naszych partnerów. W 90% przypadków możemy dostarczyć towar szybciej niż przewidywany czas dostawy producenta.

W razie potrzeby dostępne są również standardowe opcje dostawy.


„Profesjonalny, uprzejmy i dokładny. Przestarzała część wyceniona tego samego dnia i dostarczona następnego” - PT
Posiadamy akredytację ISO 9001, dzięki czemu możesz być spokojny o swój zakup.

Co mówią o nas nasi klienci

Trustpilot

1

Step 1

    Część dodana do zapytania

    2

    Krok 2

    Twój osobisty opiekun klienta już się tym zajmuje, zapewniając szybką reakcję i bezkonkurencyjną obsługę.

    3

    Krok 3

    Nie tylko przetwarzamy zamówienia – gwarantujemy sprawną dostawę, pełną przejrzystość i zero bólu głowy.

    4

    Krok 4

    Nie bez powodu zaufało nam ponad 10 000 klientów. Uzyskaj wycenę już teraz i doświadcz automatyzacji bez ryzyka, opóźnień i niepewności.