TPRSM001
SIL interface module, TeSys island, 24VDC, Isolated switching input for safe stop
Disponibile
Richiedi un preventivo adesso
| Specification | Value |
|---|---|
| Mounting Mode | horizontal and vertical 35 mm symmetrical rail) |
| Current Consumption | 10 mA |
| [Us] Rated Supply Voltage | 24 V DC supplied by the bus coupler |
| Height | 118 mm |
| Product Certifications | UL || CSA || EAC (pending) |
| Standards | IEC 60947-5-1 || UL 60947-5-1 |
| Connections - Terminals | control circuit removable spring terminal block 5 0.2-2.5 mm² AWG 24...AWG 14)rigid || control circuit removable spring terminal block 5 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit removable spring terminal block 5 0.25-2.5 mm² AWG 22...AWG 14)flexible with cable end |
| Power Dissipation In W | 0.7 W maximum |
| Net Weight | 0.159 kg |
| Safety Function | safe stop: category 0 conforming to IEC 60204-1 || safe stop: category 1 conforming to IEC 60204-1 |
| Width | 25 mm |
| Depth | 114 mm |
| Safety Level | SIL 2 conforming to IEC 61508 in single channel system architecture || SILCL 2 conforming to IEC 62061 in single channel system architecture || PL = d category 2 conforming to ISO 13849-1 in single channel system architecture |
| [Ue] Rated Operational Voltage | input/output circuit 24 V DC |
| Output Thermal Current | 8 A relay output |
| Protection Type | external fuse, 8 A gG relay output |
| Product Or Component Type | SIL interface module |
| Product Name | TeSys island |
| Range | TeSys |
| Input Type | isolated switching input safe stop |
| Device Presentation | implementation of a safe stop function for SIL motor starters TPRSS || safe stop operable for safety-related system conforming to ISO 13849-1 || operational only when connected to a bus coupler TPRBC |
| Output Type | relay instantaneous opening, 1 NO, potential free |
| Product Compatibility | TPRBC bus coupler || TPRSS SIL motor starter |
| Input Voltage | 15...28.8 V DC state 1 || 0...5 V DC state 0 |
| Local Signalling | for DS (device status) 1 LED (green/red) || for SS (safe stop status) 1 LED (green/red) |
| Input Protection Type | internal, electronic |
| Function Of Module | safe stop with 1NC or 2NC contacts monitoring |
| Overvoltage Category | III |
| [Uimp] Rated Impulse Withstand Voltage | 2 kV input/output circuit IEC 60947-1 |
| [Ui] Rated Insulation Voltage | input/output circuit 50 V |
| Device Short Name | TPRSM |
I nostri articoli usati in precedenza e le opzioni di riparazione sono coperti da 12 mesi di garanzia Obso.
“Servizio super! Tutto è stato elaborato in modo molto rapido e competente e il supporto personale è stato eccellente. Sceglierei sempre di nuovo Obso Automation! Molte grazie per l'ottimo supporto”. - MJ
Se necessario, sono disponibili anche opzioni standard per la consegna.
“Professionale, cortese e preciso. Pezzo obsoleto quotato il giorno stesso e fornito il giorno successivo” - PT
1
Step 1
Parte aggiunta per richiesta
2
Passo 2
Il vostro Account Manager personale è già al lavoro, fornendo risposte rapide e un servizio imbattibile.
3
Passo 3
Non ci limitiamo a elaborare gli ordini, ma garantiamo una consegna senza intoppi, piena trasparenza e zero grattacapi.
4
Passo 4
Più di 10.000 clienti si fidano di noi per un motivo. Richiedete subito il vostro preventivo e sperimentate l’automazione senza rischi, ritardi o incertezze.
Google Reviews