TPRPM038
Power module, TeSys island, 40A AC-1, 38A AC-3, 18.5kW, 20hp
Disponibile
Richiedi un preventivo adesso
| Specification | Value |
|---|---|
| Mounting Mode | horizontal and vertical 35 mm symmetrical DIN rail) |
| Height | 121 mm |
| Product Certifications | EAC || CCC || CSA || UL |
| Standards | EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 |
| Connections - Terminals | screw-clamp terminals 1 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 2 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 1 2.5-10 mm² AWG 14...AWG 8)flexible without cable end || screw-clamp terminals 2 2.5-10 mm² AWG 14...AWG 8)flexible without cable end || screw-clamp terminals 1 1.5-10 mm² AWG 16...AWG 10)flexible with cable end || screw-clamp terminals 2 1.5-6 mm² AWG 16...AWG 10)flexible with cable end |
| Net Weight | 0.255 kg |
| Metering Type | time device ON || number of faults || number of device power cycles || average current Iavg || average voltage Vavg || max current Imax || max voltage Vmax |
| Local Signalling | for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red) |
| Width | 45 mm |
| Depth | 115 mm |
| Tightening Torque | 2.5-2.5 N.m flat Ø 6 mm || 2.5-2.5 N.m Philips No 3 |
| Protection Type | thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || phase loss || rapid restart lockout || phase reversal || phase sequence || phase unbalance || ground current |
| Current Consumption | 60 mA |
| [Ue] Rated Operational Voltage | <= 690 V AC 47...63 Hz |
| Power Dissipation In W | 0.9 W at Ie AC-3 |
| Range Of Product | TeSys |
| Reset | remotely or automatically |
| [Ith] Conventional Free Air Thermal Current | 40 A (at 50 °C) |
| [Uc] Control Circuit Voltage | 24 V DC supplied by the bus coupler |
| Product Or Component Type | power module |
| Product Name | TeSys island |
| Thermal Overload Class | class 5…30 |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV |
| Device Presentation | power module connected to an automation controller through a bus coupler || operational only when connected to a bus coupler |
| Function Available | upstream voltage presence detection || electronic thermal overload protection || monitoring of currents || control of third party power devices when associated to TPRDG IO module |
| [Ie] Rated Operational Current | 38 A (at <50 °C) at <= 440 V AC-3 || 40 A (at <50 °C) at <= 440 V AC-1 |
| Thermal Protection Adjustment Range | 0.76-38 A |
| Product Compatibility | TPRBC bus coupler || TPRDG digital IO module || TPRAN analog IO module |
| Overvoltage Category | III |
| Maximum Horse Power Rating | 2 hp at 120 V AC 60 Hz for 1 phase motors || 5 hp at 240 V AC 60 Hz for 1 phase motors || 10 hp at 208 V AC 60 Hz for 3 phase motors || 10 hp at 240 V AC 60 Hz for 3 phase motors || 20 hp at 480 V AC 60 Hz for 3 phase motors || 25 hp at 600 V AC 60 Hz for 3 phase motors |
| Motor Power Kw | 9 kW at 230 V AC 50 Hz || 18.5 kW at 380...415 V AC 50 Hz || 18.5 kW at 440 V AC 50 Hz || 18.5 kW at 500 V AC 50 Hz || 18.5 kW at 690 V AC 50 Hz |
| [Ui] Rated Insulation Voltage | 690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1 |
| Device Short Name | TPRPM |
| Poles Description | 3P |
I nostri articoli usati in precedenza e le opzioni di riparazione sono coperti da 12 mesi di garanzia Obso.
“Servizio super! Tutto è stato elaborato in modo molto rapido e competente e il supporto personale è stato eccellente. Sceglierei sempre di nuovo Obso Automation! Molte grazie per l'ottimo supporto”. - MJ
Se necessario, sono disponibili anche opzioni standard per la consegna.
“Professionale, cortese e preciso. Pezzo obsoleto quotato il giorno stesso e fornito il giorno successivo” - PT
1
Step 1
Parte aggiunta per richiesta
2
Passo 2
Il vostro Account Manager personale è già al lavoro, fornendo risposte rapide e un servizio imbattibile.
3
Passo 3
Non ci limitiamo a elaborare gli ordini, ma garantiamo una consegna senza intoppi, piena trasparenza e zero grattacapi.
4
Passo 4
Più di 10.000 clienti si fidano di noi per un motivo. Richiedete subito il vostro preventivo e sperimentate l’automazione senza rischi, ritardi o incertezze.
Google Reviews