LC1F2100LD
Schneider Electric
contactor, TeSys F, 3P(3NO), AC-1, <=1000V 2100A, coil 200V DC
Disponibile
Richiedi un preventivo adesso
- "TeSys F contactor, 3 poles (3NO), 2100A/1000V AC-1, for non-inductive load applications. It provides a low sealed consumption 200V DC coil, bolt terminals for bars or cables with lugs. For high operating rates until 600 cycles/hour and environments until 55\u00b0C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC), Green Premium compliant (RoHS/REACh)."
| Specification | Value |
|---|---|
| Product Certifications | UL || CSA || CCC || CB Scheme || EAC || UKCA |
| Power Dissipation Per Pole | 200 W AC-1 |
| Average Impedance | 0.1 mOhm - Ith 2100 A 50 Hz |
| [Ith] Conventional Free Air Thermal Current | 2100 A (at 40 °C) |
| Control Circuit Voltage Limits | operational 0.85...1.1 Uc 55 °C) || drop-out 0.2...0.35 Uc 55 °C) |
| Standards | EN 60947-1 || IEC 60947-4-1 || JIS C8201-4-1 || EN 60947-4-1 || IEC 60947-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 |
| Mounting Support | plate |
| Control Circuit Type | DC standard |
| Hold-In Power Consumption In W | 10-10 W 20 °C |
| Rated Breaking Capacity | 3150 A conforming to IEC 60947-4-1 |
| Associated Fuse Rating | 2000 A gG at <= 440 V |
| [Uimp] Rated Impulse Withstand Voltage | 8 kV |
| Connections - Terminals | control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 4 100 x 5 mm || power circuit bolted connection |
| Pole Contact Composition | 3 NO |
| Operating Time | 50...60 ms closing || 45...60 ms opening |
| Maximum Operating Rate | 600 cyc/h 55 °C |
| Tightening Torque | control circuit 1.2 N.m || power circuit 58 N.m |
| Inrush Power In W | 2100-2100 W 20 °C) |
| Compatibility Code | LC1F |
| Overvoltage Category | III |
| [Ui] Rated Insulation Voltage | 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C || 1000 V UL 60947-4-1 |
| [Icw] Rated Short-Time Withstand Current | 10000 A 40 °C - 10 s || 7500 A 40 °C - 30 s || 5500 A 40 °C - 1 min || 4200 A 40 °C - 3 min || 3000 A 40 °C - 10 min |
| Heat Dissipation | 10-10 W |
| [Uc] Control Circuit Voltage | 200 V DC |
| Range Of Product | TeSys F |
| [Ue] Rated Operational Voltage | <= 1000 V AC 50/60 Hz || <= 460 V DC |
| Contactor Application | resistive load |
| Product Or Component Type | contactor |
| Range | TeSys |
| Utilisation Category | AC-1 |
| [Ie] Rated Operational Current | 2100 A (at <40 °C) AC AC-1 |
| Poles Description | 3P |
| Device Short Name | LC1F |
I nostri articoli usati in precedenza e le opzioni di riparazione sono coperti da 12 mesi di garanzia Obso.
“Servizio super! Tutto è stato elaborato in modo molto rapido e competente e il supporto personale è stato eccellente. Sceglierei sempre di nuovo Obso Automation! Molte grazie per l'ottimo supporto”. - MJ
Se necessario, sono disponibili anche opzioni standard per la consegna.
“Professionale, cortese e preciso. Pezzo obsoleto quotato il giorno stesso e fornito il giorno successivo” - PT
1
Step 1
Parte aggiunta per richiesta
2
Passo 2
Il vostro Account Manager personale è già al lavoro, fornendo risposte rapide e un servizio imbattibile.
3
Passo 3
Non ci limitiamo a elaborare gli ordini, ma garantiamo una consegna senza intoppi, piena trasparenza e zero grattacapi.
4
Passo 4
Più di 10.000 clienti si fidano di noi per un motivo. Richiedete subito il vostro preventivo e sperimentate l’automazione senza rischi, ritardi o incertezze.
Google Reviews