TeSys D IEC contactor, 65 A, 3 P, 40 HP at 480 VAC, nonreversing, 120 VAC 50/60 Hz coil
Disponibile
Richiedi un preventivo adesso
- "TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for any type of application. They can be used to create motor starters for almost any type of application. TeSys D contactors offer quick simple setup, while maintaining a compact size. Contactors have both Horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications. Multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs/Reach)."
| Specification | Value |
|---|---|
| Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts |
| Minimum Switching Current | 5 mA for control circuit |
| Power Dissipation Per Pole | 6.4 W AC-1 |
| Average Impedance | 1 mOhm - Ith 80 A 50 Hz for power circuit |
| Auxiliary Contact Composition | 1 NO + 1 NC |
| Terminals Description Iso N°1 | (A1-A2)CO || (13-14)NO || (21-22)NC |
| [Ith] Conventional Free Air Thermal Current | 10 A (at 60 °C) for control circuit || 80 A (at 60 °C) for power circuit |
| Control Circuit Voltage Limits | 0.3...0.6 Uc 60-60 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc 60-60 °C operational AC 50 Hz || 0.85...1.1 Uc 60-60 °C operational AC 60 Hz |
| Mounting Support | rail || plate |
| Control Circuit Type | AC 50/60 Hz |
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Insulation Resistance | > 10 MOhm for control circuit |
| Rated Breaking Capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
| Irms Rated Making Capacity | 140 A AC for control circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947 |
| Associated Fuse Rating | 10 A gG for control circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit |
| Inrush Power In Va | 140-140 VA cos phi 0.75 (at 20 °C) || 160-160 VA cos phi 0.75 (at 20 °C) |
| [Uimp] Rated Impulse Withstand Voltage | 8 kV IEC 60947 |
| Pole Contact Composition | 3 NO |
| Connections - Terminals | control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 1 1-2.5 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminal 2 1-2.5 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: flexible with cable end || power circuit: connector 1 2.5-35 mm² - cable stiffness: solid with cable end || power circuit: connector 2 2.5-35 mm² - cable stiffness: solid with cable end || power circuit: connector 1 2.5-35 mm² - cable stiffness: flexible without cable end || power circuit: connector 2 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: connector 1 2.5-35 mm² - cable stiffness: flexible with cable end || power circuit: connector 2 2.5-35 mm² - cable stiffness: flexible with cable end |
| Coil Technology | without built-in bidirectional peak limiting diode suppressor |
| Operating Time | 12...26 ms closing || 4...19 ms opening |
| Minimum Switching Voltage | 17 V for control circuit |
| Maximum Operating Rate | 3600 cyc/h 60 °C |
| Tightening Torque | control circuit 1.2 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw clamp terminal flat Ø 6 mm || power circuit 5 N.m screw clamp terminal flat Ø 8 mm |
| Mechanical Durability | 6000000 cycles |
| Auxiliary Contacts Type | mirror contact 1 NC IEC 60947-4-1 || mechanically linked 1 NO + 1 NC IEC 60947-5-1 |
| Compatibility Code | LC1D |
| Hold-In Power Consumption In Va | 13-13 VA 50 Hz cos phi 0.3 (at 20 °C) || 15-15 VA 60 Hz cos phi 0.3 (at 20 °C) |
| Overvoltage Category | III |
| Maximum Horse Power Rating | 10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA || 10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL || 20 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to CSA || 20 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to UL || 20 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to CSA || 20 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to UL || 5 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA || 5 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL || 50 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to CSA || 50 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to UL || 50 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to CSA || 50 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to UL |
| Motor Power Kw | 30 kW at 440 V AC 50/60 Hz (AC-3) || 11 kW at 400 V AC 50/60 Hz (AC-4) || 30 kW at 380...400 V AC 50/60 Hz (AC-3) || 30 kW at 415 V AC 50/60 Hz (AC-3) || 37 kW at 1000 V AC 50/60 Hz (AC-3) || 37 kW at 500 V AC 50/60 Hz (AC-3) || 37 kW at 660...690 V AC 50/60 Hz (AC-3) || 18.5 kW at 220...230 V AC 50/60 Hz (AC-3) |
| [Ui] Rated Insulation Voltage | control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1 |
| Heat Dissipation | 4-5 W at 50/60 Hz for control circuit |
| Protective Cover | with |
| [Uc] Control Circuit Voltage | 120 V AC 50/60 Hz |
| [Ue] Rated Operational Voltage | power circuit <= 690 V AC 25...400 Hz |
| Range Of Product | TeSys Deca |
| Contactor Application | motor control || resistive load |
| Product Or Component Type | contactor |
| Range | TeSys |
| Utilisation Category | AC-1 || AC-2 || AC-4 || AC-3 |
| [Ie] Rated Operational Current | 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit |
| Poles Description | 3P |
| Device Short Name | LC1D |
I nostri articoli usati in precedenza e le opzioni di riparazione sono coperti da 12 mesi di garanzia Obso.
“Servizio super! Tutto è stato elaborato in modo molto rapido e competente e il supporto personale è stato eccellente. Sceglierei sempre di nuovo Obso Automation! Molte grazie per l'ottimo supporto”. - MJ
Se necessario, sono disponibili anche opzioni standard per la consegna.
“Professionale, cortese e preciso. Pezzo obsoleto quotato il giorno stesso e fornito il giorno successivo” - PT
1
Step 1
Parte aggiunta per richiesta
2
Passo 2
Il vostro Account Manager personale è già al lavoro, fornendo risposte rapide e un servizio imbattibile.
3
Passo 3
Non ci limitiamo a elaborare gli ordini, ma garantiamo una consegna senza intoppi, piena trasparenza e zero grattacapi.
4
Passo 4
Più di 10.000 clienti si fidano di noi per un motivo. Richiedete subito il vostro preventivo e sperimentate l’automazione senza rischi, ritardi o incertezze.
Google Reviews