  • "TeSys D contactor, 3 poles (3NO), for motor control applications up to 65A/690V AC-3 (30kW@400V). It provides a 125V DC coil with transient suppressor module, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60\u00b0C, it procures high reliability and durability. Compact (55mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh)."
Per saperne di più arrow Weniger lesen arrow
Specification Value
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current 5 mA for signalling circuit
Power Dissipation Per Pole 9.6 W AC-1 || 6.3 W AC-3
Average Impedance 1.5 mOhm - Ith 80 A 50 Hz for power circuit
Auxiliary Contact Composition 1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current 10 A (at 60 °C) for signalling circuit || 80 A (at 60 °C) for power circuit
Control Circuit Voltage Limits 0.1...0.3 Uc -40-70 °C drop-out DC || 0.75...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
Mounting Support plate || rail
Contact Compatibility M4
Control Circuit Type DC standard
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree 3
Hold-In Power Consumption In W 7.4-7.4 W 20 °C
Insulation Resistance > 10 MOhm for signalling circuit
Rated Breaking Capacity 1000 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
Pole Contact Composition 3 NO
Connections - Terminals control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible without cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible without cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid without cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid without cable end
Coil Technology built-in bidirectional peak limiting diode suppressor
Time Constant 34 ms
Operating Time 42.5...57.5 ms closing || 16...24 ms opening
Minimum Switching Voltage 17 V for signalling circuit
Maximum Operating Rate 3600 cyc/h 60 °C
Signalling Circuit Frequency 25...400 Hz
Tightening Torque control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m EverLink BTR screw connectors pozidriv No 2 || power circuit 2.5 N.m EverLink BTR screw connectors pozidriv No 2
Electrical Durability 0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V
Mechanical Durability 10 Mcycles
Inrush Power In W 19-19 W 20 °C)
Auxiliary Contacts Type mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility Code LC1D
Overvoltage Category III
Maximum Horse Power Rating 40 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 5 hp at 115 V AC 50/60 Hz for 1 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 20 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 20 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 50 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Motor Power Kw 11 kW at 400 V AC 50/60 Hz (AC-4) || 18.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 30 kW at 380...400 V AC 50/60 Hz (AC-3) || 37 kW at 500 V AC 50/60 Hz (AC-3) || 37 kW at 660...690 V AC 50/60 Hz (AC-3) || 18.5 kW at 220...230 V AC 50/60 Hz (AC-3e) || 30 kW at 380...400 V AC 50/60 Hz (AC-3e) || 37 kW at 500 V AC 50/60 Hz (AC-3e) || 37 kW at 660...690 V AC 50/60 Hz (AC-3e)
[Ui] Rated Insulation Voltage power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current 640 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit || 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Protective Cover with
[Uc] Control Circuit Voltage 125 V DC
[Ue] Rated Operational Voltage power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Range Of Product TeSys Deca
Contactor Application motor control || resistive load
Product Or Component Type contactor
Range TeSys || TeSys Deca
Utilisation Category AC-4 || AC-1 || AC-3
[Ie] Rated Operational Current 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Poles Description 3P
Device Short Name LC1D
Per saperne di più arrow Weniger lesen arrow
*Gli articoli nuovi sono coperti da una garanzia Obso di 24 mesi.
I nostri articoli usati in precedenza e le opzioni di riparazione sono coperti da 12 mesi di garanzia Obso.


“Servizio super! Tutto è stato elaborato in modo molto rapido e competente e il supporto personale è stato eccellente. Sceglierei sempre di nuovo Obso Automation! Molte grazie per l'ottimo supporto”. - MJ
*La consegna e il ritiro il giorno stesso e successivo sono disponibili per le scorte delle nostre filiali nel Regno Unito e in Olanda. La consegna e il ritiro il giorno successivo e la consegna in 2 giorni sono disponibili per le scorte acquistate dai nostri partner. Nel 90% dei casi, se necessario, possiamo consegnare più velocemente del tempo previsto dal produttore.

Se necessario, sono disponibili anche opzioni standard per la consegna.


“Professionale, cortese e preciso. Pezzo obsoleto quotato il giorno stesso e fornito il giorno successivo” - PT
Siamo accreditati ISO 9001 per garantire la tranquillità del vostro acquisto.

Cosa dicono di noi i nostri clienti

Trustpilot

1

Step 1

    Parte aggiunta per richiesta

    2

    Passo 2

    Il vostro Account Manager personale è già al lavoro, fornendo risposte rapide e un servizio imbattibile.

    3

    Passo 3

    Non ci limitiamo a elaborare gli ordini, ma garantiamo una consegna senza intoppi, piena trasparenza e zero grattacapi.

    4

    Passo 4

    Più di 10.000 clienti si fidano di noi per un motivo. Richiedete subito il vostro preventivo e sperimentate l’automazione senza rischi, ritardi o incertezze.