LC2D18BL

Schneider Electric

TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 18 A - 24 V DC coil

Disponible

Obtenga una cotización ahora

  • "TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 18A/690V AC-3 (7.5kW@400V). It provides low consumption 24V DC coils with transient suppressor module, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60\u00b0C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh)."
Más información arrow Leer más arrow
Specification Value
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current 5 mA for signalling circuit
Control Circuit Voltage Limits 0.1...0.3 Uc -40-70 °C drop-out DC || 0.8...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
Hold-In Power Consumption In W 2.4-2.4 W 20 °C
Insulation Resistance > 10 MOhm for signalling circuit
Coil Technology built-in bidirectional peak limiting diode suppressor
Time Constant 40 ms
Minimum Switching Voltage 17 V for signalling circuit
Signalling Circuit Frequency 25...400 Hz
Inrush Power In W 2.4-2.4 W 20 °C)
Auxiliary Contacts Type mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Product Certifications DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
Interlocking Type mechanical
[Uc] Control Circuit Voltage 24 V DC
[Ue] Rated Operational Voltage power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Power Dissipation Per Pole 0.8 W AC-3 || 2.5 W AC-1 || 0.8 W AC-3e
Average Impedance 2.5 mOhm - Ith 32 A 50 Hz for power circuit
Auxiliary Contact Composition 1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current 10 A (at 60 °C) for signalling circuit || 32 A (at 60 °C) for power circuit
Mounting Support plate || rail
Control Circuit Type DC low consumption
Standards CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application resistive load || motor control
Rated Breaking Capacity 300 A at 440 V for power circuit conforming to IEC 60947
Product Or Component Type reversing contactor
Irms Rated Making Capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
Product Name TeSys D || TeSys Deca
Associated Fuse Rating 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
Connections - Terminals control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit screw clamp terminals 1 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 1 1-6 mm²flexible with cable end || power circuit screw clamp terminals 2 1-4 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-6 mm²solid || power circuit screw clamp terminals 2 1.5-6 mm²solid
Range TeSys || TeSys Deca
Pole Contact Composition 3 NO
Device Presentation preassembled with reversing power busbar
Utilisation Category AC-1 || AC-3 || AC-3e
[Ie] Rated Operational Current 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Maximum Operating Rate 3600 cyc/h 60 °C
Tightening Torque power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability 1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V || 1.65 Mcycles 18 A AC-3e <= 440 V
Mechanical Durability 30 Mcycles
Poles Description 3P
Operating Time 65.45...88.55 ms closing || 20...30 ms opening
Overvoltage Category III
Motor Power Kw 4 kW at 220...230 V AC 50-60 Hz || 7.5 kW at 380...400 V AC 50-60 Hz || 9 kW at 415 V AC 50-60 Hz || 9 kW at 440 V AC 50-60 Hz || 10 kW at 500 V AC 50-60 Hz || 10 kW at 660...690 V AC 50-60 Hz
Maximum Horse Power Rating 1 hp at 115 V AC 60 Hz for 1 phase motors || 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 5 hp at 230/240 V AC 60 Hz for 3 phase motors || 10 hp at 460/480 V AC 60 Hz for 3 phase motors || 15 hp at 575/600 V AC 60 Hz for 3 phase motors
[Ui] Rated Insulation Voltage power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
Device Short Name LC2D
[Icw] Rated Short-Time Withstand Current 40 A 40 °C - 10 min for power circuit || 84 A 40 °C - 1 min for power circuit || 145 A 40 °C - 10 s for power circuit || 240 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Protective Cover with
Más información arrow Leer más arrow
*Los artículos nuevos tienen hasta 24 meses de garantía Obso.
Nuestros artículos usados y opciones de reparación tienen 12 meses de garantía Obso.


«¡Súper servicio! Todo se tramitó de forma muy rápida y competente y la asistencia personal fue excelente. Siempre volvería a elegir Obso Automation. Muchas gracias por el gran apoyo». - MJ
*Entrega y recogida el mismo día y al día siguiente en nuestras sucursales del Reino Unido y Países Bajos. La entrega y recogida al día siguiente y la entrega en 2 días están disponibles para las existencias procedentes de nuestros socios. En el 90% de los casos, podemos entregar más rápido que el tiempo estimado de llegada del fabricante cuando sea necesario.

Si lo desea, también disponemos de opciones de entrega estándar.


«Profesional, cortés y preciso. Pieza obsoleta presupuestada el mismo día y suministrada al día siguiente» - PT
Contamos con la acreditación ISO 9001 para que usted esté tranquilo con su compra.

Que dicen los clientes sobre nosotros

Trustpilot

1

Step 1

    Parte agregado para la investigación

    2

    Paso 2

    Su gestor de cuenta personal ya está en ello, ofreciéndole respuestas rápidas y un servicio inmejorable.

    3

    Paso 3

    No nos limitamos a tramitar pedidos: garantizamos una entrega fluida, total transparencia y cero quebraderos de cabeza.

    4

    Paso 4

    Nuestros más de 10.000 clientes confían en nosotros por una razón. Obtenga su presupuesto ahora y experimente la automatización sin riesgos, retrasos ni incertidumbre.