LC1D95FE7

Schneider Electric

IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 115VAC 50/60Hz coil, open style

Disponible

Obtenga una cotización ahora

  • "TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 115 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.55 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product."
Más información arrow Leer más arrow
Specification Value
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current 5 mA for signalling circuit
Power Dissipation Per Pole 12.5 W AC-1 || 7.2 W AC-3 || 7.2 W AC-3e
Average Impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
Auxiliary Contact Composition 1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current 10 A (at 60 °C) for signalling circuit || 125 A (at 60 °C) for power circuit
Control Circuit Voltage Limits 0.8...1.1 Uc -40-55 °C operational AC 50 Hz || 0.85...1.1 Uc -40-55 °C operational AC 60 Hz || 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 1...1.1 Uc 55-70 °C operational AC 50/60 Hz
Mounting Support rail || plate
Contact Compatibility M11
Control Circuit Type AC 50/60 Hz standard
Safety Reliability Level B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 || B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree 3
Insulation Resistance > 10 MOhm for signalling circuit
Rated Breaking Capacity 1100 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity 1100 A at 440 V AC for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
Associated Fuse Rating 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Inrush Power In Va 245-245 VA 60 Hz cos phi 0.75 (at 20 °C) || 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
[Uimp] Rated Impulse Withstand Voltage 8 kV IEC 60947
Pole Contact Composition 3 NO
Connections - Terminals control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end || power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end || power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end || power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end || power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end || power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end
Coil Technology without built-in suppressor module
Operating Time 20...35 ms closing || 6...20 ms opening
Minimum Switching Voltage 17 V for signalling circuit
Maximum Operating Rate 3600 cyc/h 60 °C
Signalling Circuit Frequency 25...400 Hz
Tightening Torque control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Electrical Durability 1.2 Mcycles 95 A AC-3 || 1.3 Mcycles 125 A AC-1 || 1.2 Mcycles 95 A AC-3e
Mechanical Durability 4 Mcycles
Auxiliary Contacts Type mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility Code LC1D
Hold-In Power Consumption In Va 26-26 VA 60 Hz cos phi 0.3 (at 20 °C) || 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
Overvoltage Category III
Maximum Horse Power Rating 7.5 hp at 120 V AC 60 Hz for 1 phase motors || 15 hp at 230/240 V AC 60 Hz for 1 phase motors || 30 hp at 200/208 V AC 60 Hz for 3 phase motors || 30 hp at 230/240 V AC 60 Hz for 3 phase motors || 60 hp at 460/480 V AC 60 Hz for 3 phase motors || 60 hp at 575/600 V AC 60 Hz for 3 phase motors
Motor Power Kw 25 kW at 220...230 V AC 50 Hz (AC-3) || 45 kW at 380...400 V AC 50 Hz (AC-3) || 45 kW at 415...440 V AC 50 Hz (AC-3) || 55 kW at 500 V AC 50 Hz (AC-3) || 45 kW at 660...690 V AC 50 Hz (AC-3) || 15 kW at 400 V AC 50 Hz (AC-4) || 25 kW at 220...230 V AC 50 Hz (AC-3e) || 45 kW at 380...400 V AC 50 Hz (AC-3e) || 45 kW at 415...440 V AC 50 Hz (AC-3e) || 55 kW at 500 V AC 50 Hz (AC-3e) || 45 kW at 660...690 V AC 50 Hz (AC-3e)
[Ui] Rated Insulation Voltage power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
[Icw] Rated Short-Time Withstand Current 1100 A 40 °C - 1 s for power circuit || 800 A 40 °C - 10 s for power circuit || 400 A 40 °C - 1 min for power circuit || 135 A 40 °C - 10 min for power circuit || 140 A - 100 ms for signalling circuit || 120 A - 500 ms for signalling circuit || 100 A - 1 s for signalling circuit
Heat Dissipation 6-10 W at 50/60 Hz
Protective Cover with
[Uc] Control Circuit Voltage 115 V AC 50/60 Hz
[Ue] Rated Operational Voltage power circuit <= 690 V AC 25...400 Hz
Range Of Product TeSys Deca
Contactor Application motor control || resistive load
Product Or Component Type contactor
Range TeSys
Utilisation Category AC-3 || AC-3e || AC-4 || AC-1
[Ie] Rated Operational Current 95 A (at <60 °C) at <= 440 V AC-3 for power circuit || 125 A (at <60 °C) at <= 690 V AC-1 for power circuit || 95 A (at <60 °C) at <= 440 V AC-3e for power circuit
Poles Description 3P
Device Short Name LC1D
Más información arrow Leer más arrow
*Los artículos nuevos tienen hasta 24 meses de garantía Obso.
Nuestros artículos usados y opciones de reparación tienen 12 meses de garantía Obso.


«¡Súper servicio! Todo se tramitó de forma muy rápida y competente y la asistencia personal fue excelente. Siempre volvería a elegir Obso Automation. Muchas gracias por el gran apoyo». - MJ
*Entrega y recogida el mismo día y al día siguiente en nuestras sucursales del Reino Unido y Países Bajos. La entrega y recogida al día siguiente y la entrega en 2 días están disponibles para las existencias procedentes de nuestros socios. En el 90% de los casos, podemos entregar más rápido que el tiempo estimado de llegada del fabricante cuando sea necesario.

Si lo desea, también disponemos de opciones de entrega estándar.


«Profesional, cortés y preciso. Pieza obsoleta presupuestada el mismo día y suministrada al día siguiente» - PT
Contamos con la acreditación ISO 9001 para que usted esté tranquilo con su compra.

Que dicen los clientes sobre nosotros

Trustpilot

1

Step 1

    Parte agregado para la investigación

    2

    Paso 2

    Su gestor de cuenta personal ya está en ello, ofreciéndole respuestas rápidas y un servicio inmejorable.

    3

    Paso 3

    No nos limitamos a tramitar pedidos: garantizamos una entrega fluida, total transparencia y cero quebraderos de cabeza.

    4

    Paso 4

    Nuestros más de 10.000 clientes confían en nosotros por una razón. Obtenga su presupuesto ahora y experimente la automatización sin riesgos, retrasos ni incertidumbre.