LC1D386CD
Schneider Electric
IEC contactor, TeSys Deca, nonreversing, 38A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 36VDC coil, open style
Verfügbar
Jetzt Angebot einholen
- "TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 36 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product."
| Specification | Value |
|---|---|
| Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact |
| Minimum Switching Current | 5 mA for signalling circuit |
| Power Dissipation Per Pole | 5 W AC-1 || 3 W AC-3 || 3 W AC-3e |
| Average Impedance | 2 mOhm - Ith 50 A 50 Hz for power circuit |
| Auxiliary Contact Composition | 1 NO + 1 NC |
| [Ith] Conventional Free Air Thermal Current | 10 A (at 60 °C) for signalling circuit || 50 A (at 60 °C) for power circuit |
| Control Circuit Voltage Limits | 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC |
| Mounting Support | plate || rail |
| Contact Compatibility | M4 |
| Control Circuit Type | DC standard |
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Pollution Degree | 3 |
| Hold-In Power Consumption In W | 5.4-5.4 W 20 °C |
| Insulation Resistance | > 10 MOhm for signalling circuit |
| Rated Breaking Capacity | 550 A at 440 V for power circuit conforming to IEC 60947 |
| Irms Rated Making Capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947 |
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947 |
| Pole Contact Composition | 3 NO |
| Connections - Terminals | control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 10 mm |
| Coil Technology | built-in bidirectional peak limiting diode suppressor |
| Time Constant | 28 ms |
| Operating Time | 16...24 ms opening || 53.55...72.45 ms closing |
| Minimum Switching Voltage | 17 V for signalling circuit |
| Maximum Operating Rate | 3600 cyc/h 60 °C |
| Signalling Circuit Frequency | 25...400 Hz |
| Tightening Torque | control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2 |
| Electrical Durability | 1.4 Mcycles 50 A AC-1 <= 440 V || 1.4 Mcycles 38 A AC-3 <= 440 V || 1.4 Mcycles 38 A AC-3e <= 440 V |
| Mechanical Durability | 30 Mcycles |
| Inrush Power In W | 5.4-5.4 W 20 °C) |
| Auxiliary Contacts Type | mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1 |
| Compatibility Code | LC1D |
| Overvoltage Category | III |
| Maximum Horse Power Rating | 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 240 V AC 50/60 Hz for 1 phase motors || 20 hp at 480 V AC 50/60 Hz for 3 phase motors || 25 hp at 600 V AC 50/60 Hz for 3 phase motors |
| Motor Power Kw | 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) || 18.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 9 kW at 220...230 V AC 50/60 Hz (AC-3) || 18.5 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3e) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3e) || 18.5 kW at 380...400 V AC 50/60 Hz (AC-3e) || 9 kW at 220...230 V AC 50/60 Hz (AC-3e) || 18.5 kW at 415...440 V AC 50/60 Hz (AC-3e) |
| [Ui] Rated Insulation Voltage | power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1 |
| [Icw] Rated Short-Time Withstand Current | 60 A 40 °C - 10 min for power circuit || 430 A 40 °C - 1 s for power circuit || 150 A 40 °C - 1 min for power circuit || 310 A 40 °C - 10 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit |
| Protective Cover | with |
| [Uc] Control Circuit Voltage | 36 V DC |
| [Ue] Rated Operational Voltage | power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC |
| Range Of Product | TeSys Deca |
| Contactor Application | motor control || resistive load |
| Product Or Component Type | contactor |
| Range | TeSys || TeSys Deca |
| Utilisation Category | AC-4 || AC-1 || AC-3 || AC-3e |
| [Ie] Rated Operational Current | 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 38 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
| Poles Description | 3P |
| Device Short Name | LC1D |
Auf unsere gebrauchten Artikel und Reparaturoptionen gewähren wir 12 Monate Obso-Garantie.
„Super Service! Alles wurde sehr schnell und kompetent abgewickelt und die persönliche Betreuung war hervorragend. Ich würde mich jederzeit wieder für Obso Automation entscheiden! Vielen Dank für die tolle Unterstützung.“ - MJ
Bei Bedarf sind auch Standardoptionen für die Lieferung verfügbar.
„Professionell, zuvorkommend und genau. Veraltetes Teil am selben Tag angeboten und am nächsten Tag geliefert“ - PT
1
Step 1
Bauteil zur Anfrage hinzugefügt
2
Seite 2
Ihr persönlicher Kundenbetreuer ist bereits dabei und sorgt für schnelle Antworten und einen unschlagbaren Service.
3
Seite 3
Wir wickeln nicht nur Aufträge ab – wir garantieren eine reibungslose Lieferung, volle Transparenz und keine Kopfschmerzen.
4
Seite 4
Mehr als 10.000 Kunden vertrauen uns aus gutem Grund. Fordern Sie jetzt Ihr Angebot an und erleben Sie Automatisierung ohne Risiko, Verzögerungen oder Unsicherheit.
Google Reviews