TM3SAK6RG
Schneider Electric
safety module, Modicon TM3, 3 function, Cat 4 PL e, SIL CL3, spring, 24V DC
AVAILABLE
GET A QUOTE NOW
- "This TM3 safety expansion module monitors emergency shutdown pushbuttons, limit switches, light curtains and safety mats/edges. It meets the requirements of PL e/Category 4 conforming to EN/ISO 13849-1 and SILCL3 conforming to EN/IEC 62061. It has a module locking latch, 2 TM3 bus connectors designed to provide continuity of the link between connected modules, a symmetrical rail locking clip, display block for the module channels and diagnostics. It completes your Modicon M221, M241 or M251 PLC configuration with a dedicated safety I/O, without the need to use a complete safety controller. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It is compatible with emergency push buttons, limit switches, safety light curtains and safety mats/edges, the 4 most common safety sensors in the industry. It has spring terminals for fast and reliable wiring of safety circuits."
| Specification | Value |
|---|---|
| Range Of Product | Modicon TM3 Safety |
| Product Or Component Type | safety module |
| Safety Module Application | for emergency stop, switch, sensing mat/edges or safety light curtain monitoring |
| Function Of Module | emergency stop monitoring 1-channel wiring || emergency stop monitoring 2-channel wiring || monitoring of a movable guard with 2 switches and automatic start || monitoring of a movable guard || multiple emergency stop monitoring 2-channel wiring || proximity sensor monitoring PNP/PNP || proximity sensor monitoring PNP/NPN || sensing mat and edges monitoring || monitoring of electro-sensitive protection equipment (ESPE) PNP/PNP || monitoring of electro-sensitive protection equipment (ESPE) PNP/NPN |
| Device Short Name | TM3SAK |
| Safety Level | can reach PL e/category 4 ISO 13849-1 2008 || can reach PL e/category 4 ISO 13849-2 2012 || can reach SILCL 3 IEC 62061 2005 || can reach SIL 3 IEC 61508 2010 |
| Product Certifications | CSA 61010-2-201 (pending) || TÜV || CSA Haz Loc Class 1 Division 2 (pending) || EAC || RCM || UL 61010-2-201 || ANSI Haz Loc Class 1 Division 2 (pending) |
| Output Voltage | 10 V relay output |
| Power Consumption In W | 0.2 W 5 V DC || 3.6 W 24 V DC |
| [Uc] Control Circuit Voltage | 24 V DC |
| Height | 94 mm |
| Standards | ISO 13849-1:2008 || ISO 13849-2:2012 || IEC 62061:2005 || IEC 61508:2010 || IEC 60947-5-1:2010 || IEC 61131-2:2007 || IEC 60204-1:2005 || IEC 60204-1:2009/A1 || IEC 61010-1:2010 || EN 50581:2012 |
| Output Thermal Current | 6 A per relay relay output |
| Connections - Terminals | captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals || captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals || captive spring terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals || captive spring terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals |
| Product Compatibility | safety light curtains EN/IEC 61496-1 (type 4) || sensing mat/edges EN 1760-1 |
| Electromagnetic Compatibility | electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 || electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 || susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3 || susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 || susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3 || magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 || electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4 || electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4 || 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 || conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 || radiated emission - test level: 40 dBµV/m class A (24 V) conforming to IEC 55011 || radiated emission - test level: 47 dBµV/m class A (24 V) conforming to IEC 55011 |
| Minimum Output Current | 10 mA relay output |
| Marking | CSA || RCM || UL || EFUP 10 || CE || TÜV || EAC |
| [Ith] Conventional Free Air Thermal Current | 18 A |
| Associated Fuse Rating | 4 A gG or gL relay output IEC 60947-5-1 || 6 A fast blow relay output IEC 60947-5-1 |
| [Uimp] Rated Impulse Withstand Voltage | 4 kV III IEC 60647-5-1 |
| Net Weight | 0.19 kg |
| Current Consumption | 100 mA 24 V DC external supply |
| Output Type | relay instantaneous opening, 3 NO, potential free |
| [Us] Rated Supply Voltage | 24 V - 15...20 % DC |
| [Ui] Rated Insulation Voltage | 300 V 2)IEC 60647-5-1 |
| Mounting Support | top hat type TH35-7.5 rail IEC 60715 || top hat type TH35-15 rail IEC 60715 || wall mount using attached fasteners |
| Local Signalling | for user 8 LEDs (green/red) |
| Maximum Switching Voltage | 230 V AC-15 50 Hz relay instantaneous opening) || 24 V DC-13 relay instantaneous opening) |
| Electrical Connection | spring terminal |
| Safety Reliability Data | DC = 95 % ISO 13849-1 || PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A || PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A || MTTFd = 500 years ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A || MTTFd = 85 years ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A || SFF = 95 % IEC 61508-1 || HFT = 1 IEC 61508-1 || type = A IEC 61508-1 |
| Input Protection Type | internal, electronic |
| Width | 43.7 mm |
| Number Of Safety Circuits | 3 NO relay instantaneous opening |
| Depth | 73 mm |
| Synchronisation Time Between Inputs | unlimited || 2 or 4 s depending of wiring configurable by software |
| Maximum Cable Distance Between Devices | 30 m |
| Maximum Response Time On Input Open | 40 ms |
| Breaking Capacity | 4 A 24 V 50 ms DC-13 relay output |
| Breaking Capacity | 360 VA holding AC-15 B300 relay output || 3600 VA inrush AC-15 B300 relay output |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews






