TM3SAC5RG
Schneider Electric
safety module, Modicon TM3, 1 function, Cat 3 PL d, SIL CL2, spring, 24V DC
AVAILABLE
GET A QUOTE NOW
- "This TM3 safety expansion module monitors emergency shutdown pushbuttons and limit switches to conform to PLd / Category 3. It meets the requirements of PL d/Category 3 conforming to EN/ISO 13849-1 and SILCL 2 conforming to EN/IEC 62061. It has a module locking latch, 2 TM3 bus connectors designed to provide continuity of the link between connected modules, a symmetrical rail locking clip, display block for the module channels and diagnostics. It completes your Modicon M221, M241 or M251 PLC configuration with a dedicated safety I/O, without the need to use a complete safety controller. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It has spring terminals for fast and reliable wiring of safety circuits."
| Specification | Value |
|---|---|
| Product Certifications | UL 61010-2-201 || CSA 61010-2-201 (pending) || TÜV || EAC || CSA Haz Loc Class 1 Division 2 (pending) || ANSI Haz Loc Class 1 Division 2 (pending) || RCM |
| Output Voltage | 10 V relay output |
| Power Consumption In W | 0.2 W 5 V DC || 3.6 W 24 V DC |
| [Uc] Control Circuit Voltage | 24 V DC |
| Height | 94 mm |
| Standards | ISO 13849-1:2008 || ISO 13849-2:2012 || IEC 62061:2005 || IEC 61508:2010 || IEC 60947-5-1:2010 || IEC 61131-2:2007 || IEC 60204-1:2005 || IEC 60204-1:2009/A1 || IEC 61010-1:2010 || EN 50581:2012 |
| Output Thermal Current | 6 A per relay relay output |
| Connections - Terminals | captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 || captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals || captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals || captive spring terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals || captive spring terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals |
| Electromagnetic Compatibility | electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 || electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 || susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3 || susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 || susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3 || magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 || electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4 || electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4 || 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 || conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 || radiated emission - test level: 40 dBµV/m class A (24 V) conforming to IEC 55011 || radiated emission - test level: 47 dBµV/m class A (24 V) conforming to IEC 55011 |
| Minimum Output Current | 10 mA relay output |
| Marking | CSA || EAC || CE || RCM || UL || TÜV || EFUP 10 |
| [Ith] Conventional Free Air Thermal Current | 18 A |
| Associated Fuse Rating | 4 A gG or gL relay output IEC 60947-5-1 || 6 A fast blow relay output IEC 60947-5-1 |
| [Uimp] Rated Impulse Withstand Voltage | 4 kV III IEC 60647-5-1 |
| Net Weight | 0.19 kg |
| Current Consumption | 100 mA 24 V DC external supply |
| Output Type | relay instantaneous opening, 3 NO, potential free |
| [Us] Rated Supply Voltage | 24 V - 15...20 % DC |
| [Ui] Rated Insulation Voltage | 300 V 2)IEC 60647-5-1 |
| Mounting Support | top hat type TH35-7.5 rail IEC 60715 || top hat type TH35-15 rail IEC 60715 || wall mount using attached fasteners |
| Local Signalling | for user 6 LEDs (green/red) |
| Maximum Switching Voltage | 230 V AC-15 50 Hz relay instantaneous opening) || 24 V DC-13 relay instantaneous opening) |
| Electrical Connection | spring terminal |
| Safety Reliability Data | DC = 95 % ISO 13849-1 || SFF = 95 % IEC 61508-1 || HFT = 1 IEC 61508-1 || type = A IEC 61508-1 || PFHd = 5E-9 1/h IEC 61508-1 || PFHd = 30E-9 1/h IEC 61508-1 || MTTFd = 500 years ISO 13849-1 || MTTFd = 85 years ISO 13849-1 |
| Input Protection Type | internal, electronic |
| Width | 43.7 mm |
| Number Of Safety Circuits | 3 NO relay instantaneous opening |
| Depth | 73 mm |
| Synchronisation Time Between Inputs | unlimited |
| Maximum Cable Distance Between Devices | 30 m |
| Maximum Response Time On Input Open | 40 ms |
| Breaking Capacity | 4 A 24 V 50 ms DC-13 relay output |
| Breaking Capacity | 360 VA holding AC-15 B300 relay output || 3600 VA inrush AC-15 B300 relay output |
| Range Of Product | Modicon TM3 Safety |
| Product Or Component Type | safety module |
| Safety Module Application | for emergency stop and switch monitoring |
| Function Of Module | emergency stop monitoring 1-channel wiring || emergency stop monitoring 2-channel wiring || monitoring of a movable guard with 2 switches and automatic start |
| Device Short Name | TM3SAC |
| Safety Level | can reach PL d/category 3 ISO 13849-1 2008 || can reach PL d/category 3 ISO 13849-2 2012 || can reach SILCL 2 IEC 62061 2005 || can reach SIL 2 IEC 61508 2010 |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews