- "This Harmony RM35-LM relay allows monitoring of level control in 3-phase networks. This modular multi function 3-phase liquid level control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0"
| Specification | Value |
|---|---|
| [Us] Rated Supply Voltage | 24...240 V AC/DC 50/60 Hz +/- 10 % |
| Safety Reliability Data | B10d = 170000 || MTTFd = 182.6 years |
| Control Circuit Voltage Limits | 15 % + 10 % Un |
| Cable Capacitance | 1 nF HS (High Sensitivity) probe cable || 2.2 nF St (Standard Sensitivity) probe cable || 4.7 nF LS (Low Sensitivity) |
| Insulation Resistance | > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 || > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 || > 1 MOhm 500 V DC between supply and measurement IEC 60664-1 |
| Measurement Error | 0.5 %/°C with temperature variation |
| Operating Rate | <= 360 operations/hour full load |
| Output Contacts | 2 C/O |
| Reset Time | 1750 ms |
| Marking | CE : 73/23/EEC || CE : EMC 89/336/EEC |
| Operating Position | any position without derating |
| Sensitivity Scale | 0.25...5 kOhm LS (Low Sensitivity) || 5...100 kOhm St (Standard Sensitivity) || 50...1000 kOhm HS (High Sensitivity) |
| Maximum Switching Voltage | 250 V AC/DC |
| Connections - Terminals | screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end |
| [Ui] Rated Insulation Voltage | 250 V IEC 60664-1 |
| Overvoltage Category | III IEC 60664-1 |
| Supply Voltage Limits | 20.4-264 V AC/DC |
| Mounting Support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Nominal Output Current | 5 A |
| Local Signalling | for relay ON LED (yellow) || for power ON LED (green) || for timer ON LED (yellow) |
| Mechanical Durability | 30000000 cycles |
| Maximum Supply Current For Sensors | 1 mA |
| Housing Material | self-extinguishing plastic |
| Measurement Accuracy | +/- 10 % of the full scale value || +/- 20 % for the HS range |
| Width | 35 mm |
| Tightening Torque | 0.6-1 N.m IEC 60947-1 |
| Maximum Power Consumption In W | 1.5 W DC |
| Sensitivity Adjustment | 5-100 % |
| Electrical Durability | 100000 cycles |
| Run-Up Delay At Power-Up | 0.6 s |
| Repeat Accuracy | +/- 2 % time delay |
| Minimum Switching Current | 10 mA 5 V DC |
| Maximum Switching Current | 5 A AC/DC |
| Range Of Product | Harmony Control Relays |
| Measurement Range | 250 Ohm...1 MOhm |
| Switching Capacity In Va | 1250 VA |
| Product Or Component Type | level control relay |
| Utilisation Category | AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 |
| Relay Name | RM35L |
| Contacts Type And Composition | 2 C/O |
| Relay Type | level control relay |
| Time Delay Type | adjustable 0.1...5 s, +/- 10 % |
| Relay Monitored Parameters | detection by resistive probes |
| Maximum Power Consumption In Va | 5 VA AC |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews