RM22JA21MR
current control relay, Harmony Control Relays , 8A, 2CO, 24…240V AC DC
AVAILABLE
GET A QUOTE NOW
| Specification | Value |
|---|---|
| [Us] Rated Supply Voltage | 24...240 V AC/DC 50/60 Hz +/- 10 % |
| Safety Reliability Data | MTTFd = 296.8 years || B10d = 270000 |
| Maximum Measuring Cycle | 100 ms measurement cycle as true rms value |
| Switching Threshold Drift | <= 0.05 % per degree centigrade depending permissible ambient air temperature || <= 1 % within the supply voltage range |
| Control Circuit Voltage Limits | 15 % + 10 % Un |
| Hysteresis | 5-50 % adjustable threshold setting |
| Insulation Resistance | > 100 MOhm 500 V DC IEC 60255-27 |
| Measurement Error | < 1 % over the whole range with voltage variation || 0.05 %/°C with temperature variation |
| Internal Input Resistance | 0.1 Ohm || 2.5 Ohm || 0.5 Ohm |
| Output Contacts | 2 C/O |
| Contacts Material | cadmium free |
| Response Time | <= 500 ms |
| Net Weight | 0.11 kg |
| Threshold Setting | 10...100 % |
| Maximum Switching Voltage | 250 V AC |
| Reset Time | 1500 ms at maximum voltage |
| Connections - Terminals | screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end |
| Overvoltage Category | III IEC 60664-1 || III UL 508 |
| Insulation | between supply and measurement |
| Time Delay Drift | <= 0.05 % per degree centigrade depending permissible ambient air temperature || <= 1 % within the supply voltage range |
| Setting Accuracy Of Time Delay | 10 P |
| Supply Voltage Limits | 20.4-264 V AC/DC |
| Mounting Support | 35 mm DIN rail conforming to IEC 60715 |
| Nominal Output Current | 8 A |
| Local Signalling | for relay ON LED (yellow) || for power ON LED (green) |
| Mechanical Durability | 10000000 cycles |
| Housing Material | self-extinguishing plastic |
| Resistance Across Terminals | 2.5 Ohm E1-M terminals || 0.5 Ohm E2-M terminals || 0.1 Ohm E3-M terminals |
| Width | 22.5 mm |
| Tightening Torque | 0.6-1 N.m IEC 60947-1 |
| Maximum Power Consumption In W | 1.5 W DC |
| Electrical Durability | 100000 cycles |
| Run-Up Delay At Power-Up | 0.3 s |
| Repeat Accuracy | +/- 0.5 % input and measurement circuit || +/- 0.2 % time delay |
| Setting Accuracy Of The Switching Threshold | +/- 10 % of the full scale |
| Minimum Switching Current | 10 mA 5 V DC |
| Maximum Switching Current | 8 A AC |
| Range Of Product | Harmony Control Relays |
| Measurement Range | 4...40 mA E1-M terminals || 20...200 mA E2-M terminals || 100...1000 mA E3-M terminals || 4 mA...1 A current AC/DC 50/60 Hz |
| Switching Capacity In Va | 2000 VA |
| Product Or Component Type | current control relay |
| Utilisation Category | AC-15 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || AC-1 IEC 60947-4-1 || DC-1 IEC 60947-4-1 |
| Relay Name | RM22JA |
| Contacts Type And Composition | 2 C/O |
| Relay Type | current control relay |
| Time Delay Type | without |
| Relay Monitored Parameters | overcurrent detection |
| Maximum Power Consumption In Va | 3.5 VA |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews