| Specification | Value |
|---|---|
| Voltage Range | 208...480 V phase to phase |
| Safety Reliability Data | MTTFd = 502.2 years || B10d = 470000 |
| Minimum Switching Current | 10 mA 5 V DC |
| Maximum Measuring Cycle | 150 ms measurement cycle as true rms value |
| Control Circuit Voltage Limits | 12 % + 10 % Un |
| Maximum Switching Current | 5 A AC || 5 A DC |
| Hysteresis | 2-2 % |
| Insulation Resistance | > 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1 |
| Measurement Error | < 0.05 %/°C with temperature variation || < 1 % over the whole range with voltage variation |
| Operating Rate | <= 360 operations/hour full load |
| Phase Failure Sensitivity | 0.7 Un |
| Power Consumption In Va | 0-22 VA 400 V AC 50 Hz |
| Output Contacts | 1 C/O |
| Adjustment Of Asymmetry Threshold | 5...15 % of Un selected |
| Marking | CE |
| Response Time | < 200 ms (in the event of a fault) |
| Operating Position | any position without derating |
| Utilisation Category | AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 |
| Net Weight | 0.13 kg |
| Maximum Switching Voltage | 250 V AC || 250 V DC |
| Measurement Voltage Limits | 183-528 V AC |
| Reset Time | 1500 ms time delay |
| Connections - Terminals | screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end |
| [Ui] Rated Insulation Voltage | 400 V IEC 60664-1 |
| Overvoltage Category | III IEC 60664-1 |
| Supply Voltage Limits | 183-528 V AC |
| Mounting Support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Nominal Output Current | 5 A |
| Local Signalling | for power ON LED (green) || for relay ON LED (yellow) |
| Mechanical Durability | 30000000 cycles |
| Housing Material | self-extinguishing plastic |
| Control Circuit Frequency | 50...60 Hz +/- 10 % |
| Threshold Adjustment Voltage | -2...-12 % in the range 208 V AC || -2...-17 % in the range 220 V AC || 2...20 % of Un selected || +2...+10 % in the range 480 V AC |
| Width | 17.5 mm |
| Tightening Torque | 0.6-1 N.m IEC 60947-1 |
| Electrical Durability | 100000 cycles |
| Run-Up Delay At Power-Up | 650 ms |
| Supply Frequency | 50/60 Hz +/- 10 % |
| Repeat Accuracy | 0.5 % input and measurement circuit || 3 % time delay |
| Range Of Product | Harmony Control Relays |
| Measurement Range | 208...480 V voltage AC |
| Switching Capacity In Va | 1250 VA |
| Product Or Component Type | 3-phase control relay |
| Relay Name | RM17TU |
| Contacts Type And Composition | 1 C/O |
| Relay Type | multifunction control relay |
| Product Specific Application | for 3-phase supply |
| Time Delay Type | adjustable 0.1...10 s, +/- 10 % of the full scale value |
| Relay Monitored Parameters | undervoltage detection || phase sequence || phase failure detection |
| [Uc] Control Circuit Voltage | 208...480 V |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews