LUCDX6FU
Schneider Electric
Advanced control unit, TeSys Ultra, 0.15A to 0.6A, 3P motors, protection & diagnostic, class 20, coil 110-240VAC/DC
AVAILABLE
GET A QUOTE NOW
- "TeSys U control and diagnostic unit to be inserted in advanced power bases LUB120, LUB320, LUB380 to form a TeSys U starter controller, for 3-phase motor applications up to 0.09kW@400V. It provides full protection to motors with a rated current Ir 0.15-0.6A (Ir adjustable), overload tripping class 20, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). For diagnostics, it provides a thermal overload alarm to be managed with an additional function module (to be ordered separately) and a test push button for overload simulation. To be used with a 110-240V AC / 110-220V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh)."
| Specification | Value |
|---|---|
| Product Certifications | CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine |
| Height | 66 mm |
| Reset | manual reset |
| Fixing Mode | plug-in front face) |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947-6-2 |
| Standards | EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier |
| Typical Current Consumption | 280 mA 110...240 V AC I maximum while closing with LUB12 || 280 mA 110...240 V AC I maximum while closing with LUB32 || 280 mA 110...240 V AC I maximum while closing with LUB38 || 280 mA 110...220 V DC I maximum while closing with LUB12 || 280 mA 110...220 V DC I maximum while closing with LUB32 || 280 mA 110...220 V DC I maximum while closing with LUB38 || 35 mA 110...240 V AC I rms sealed with LUB12 || 25 mA 110...240 V AC I rms sealed with LUB32 || 25 mA 110...240 V AC I rms sealed with LUB38 || 35 mA 110...220 V DC I rms sealed with LUB12 || 25 mA 110...220 V DC I rms sealed with LUB32 || 25 mA 110...220 V DC I rms sealed with LUB38 |
| [Ui] Rated Insulation Voltage | 690 V IEC 60947-6-2 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1 |
| Compatibility Code | LUCD |
| Control Circuit Voltage Limits | 88...264 V AC 110...240 V in operation || 88...242 V DC 110...220 V in operation || 55 V AC 110...240 V drop-out || 55 V DC 110...220 V drop-out |
| Operating Time | 35 ms opening with LUB12 control circuit || 35 ms opening with LUB32 control circuit || 35 ms opening with LUB38 control circuit || 50 ms closing with LUB12 control circuit || 50 ms closing with LUB32 control circuit || 50 ms closing with LUB38 control circuit |
| Width | 45 mm |
| Safe Separation Of Circuit | 400 V SELV between the control and auxiliary circuits IEC 60947-1 || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 |
| Depth | 60 mm |
| Heat Dissipation | 2-2 W control circuit with LUB12 || 3-3 W control circuit with LUB32 || 3-3 W control circuit with LUB38 |
| [Uc] Control Circuit Voltage | 110...240 V AC || 110...220 V DC |
| [Ue] Rated Operational Voltage | 690 V AC |
| Range Of Product | TeSys Ultra |
| Phase Failure Sensitivity | yes |
| Thermal Protection Adjustment Range | 0.15-0.6 A |
| Product Or Component Type | advanced control unit |
| Product Name | TeSys Ultra |
| Thermal Overload Class | class 20 40-60 Hz -25-70 °C IEC 60947-6-2 || class 20 40-60 Hz -25-70 °C UL 508 |
| Motor Power Kw | 0.09 kW 400...440 V AC 50/60 Hz |
| Range | TeSys |
| Utilisation Category | AC-44 || AC-43 || AC-41 |
| Function Available | protection against overload and short-circuit || protection against phase failure and phase imbalance || manual reset || earth fault protection |
| Tripping Threshold | 14.2 x Ir +/- 20 % |
| Product Compatibility | power base LUB12 || power base LUB32 || power base LUB38 || power base LUB120 || power base LUB320 || power base LUB380 || reversing contactor breaker LU2B12FU || reversing contactor breaker LU2B32FU || reversing contactor breaker LU2B38FU |
| Product Specific Application | basic protection and advanced functions, communication |
| Network Frequency | 40...60 Hz |
| Load Type | 3-phase motor self-cooled |
| Device Application | motor control || motor protection |
| Device Short Name | LUCD |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews