LUB32
Power base, TeSys Ultra, 32 A, screw clamps control
AVAILABLE
GET A QUOTE NOW
| Specification | Value |
|---|---|
| [Ics] Rated Service Breaking Capacity | 50 kA 230 V || 50 kA 440 V || 10 kA 500 V || 4 kA 690 V |
| [Ue] Rated Operational Voltage | 690 V AC power circuit |
| Auxiliary Contact Composition | 1 NO + 1 NC |
| [Uc] Control Circuit Voltage | 24 V AC 50/60 Hz || 24 V DC || 48...72 V AC 50/60 Hz || 48...72 V DC || 110...240 V AC 50/60 Hz || 110...220 V DC |
| Product Or Component Type | non reversing power base |
| [Ith] Conventional Free Air Thermal Current | 32 A |
| Product Name | TeSys Ultra |
| Range | TeSys |
| Utilisation Category | AC-43 || AC-44 || AC-41 |
| [Ie] Rated Operational Current | 28.5 A <= 440 V || 23 A 500 V || 21 A 690 V |
| Suitability For Isolation | yes |
| Auxiliary Contacts Type | linked contacts 1 NO + 1 NC) IEC 60947-4-1 || mirror contact 1 NC) IEC 60947-1 |
| Poles Description | 3P |
| Network Frequency | 40...60 Hz |
| Device Application | motor control || motor protection |
| Device Short Name | LUB |
| Product Certifications | CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine |
| Height | 154 mm |
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Maximum Operating Rate | 3600 cyc/h |
| Connections - Terminals | control circuit screw clamp terminals 1 0.34-1.5 mm² flexible with cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² flexible without cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² rigid || control circuit screw clamp terminals 2 0.34-1.5 mm² flexible with cable end || control circuit screw clamp terminals 2 0.75-1.5 mm² flexible without cable end || control circuit screw clamp terminals 2 0.75-1.5 mm² rigid || power circuit screw clamp terminals 1 1-10 mm² rigid || power circuit screw clamp terminals 1 1-6 mm² flexible with cable end || power circuit screw clamp terminals 1 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 2 1-6 mm² flexible with cable end || power circuit screw clamp terminals 2 1-6 mm² rigid || power circuit screw clamp terminals 2 1.5-6 mm² flexible without cable end |
| Net Weight | 0.9 kg |
| Fixing Mode | clipped DIN rail) || screw-fixed plate) |
| [Uimp] Rated Impulse Withstand Voltage | 6 kVIEC 60947-6-2 |
| Standards | EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier |
| [Ui] Rated Insulation Voltage | 690 V IEC 60947-6-2 3) || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1 |
| Typical Current Consumption | 200 mA 24 V DC I maximum while closing with LUCM || 220 mA 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD || 220 mA 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD || 25 mA 110...220 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD || 25 mA 110...240 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD || 280 mA 110...220 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD || 280 mA 110...240 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD || 280 mA 48...72 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD || 280 mA 48...72 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD || 45 mA 48...72 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD || 45 mA 48...72 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD || 75 mA 24 V DC I rms sealed with LUCM || 80 mA 24 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD || 90 mA 24 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD |
| Mechanical Durability | 15 Mcycles |
| Compatibility Code | LUB |
| Operating Time | 35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM control circuit || 50 ms >= 72 V closing with LUCA, LUCB, LUCC, LUCD control circuit || 60 ms 48 V closing with LUCA, LUCB, LUCC, LUCD control circuit || 70 ms 24 V closing with LUCA, LUCB, LUCC, LUCD control circuit || 65 ms closing with LUCM control circuit |
| Width | 45 mm |
| Tightening Torque | control circuit 0.8-1.2 N.m flat 5 mm || control circuit 0.8-1.2 N.m Philips no 1 5 mm || power circuit 1.9-2.5 N.m flat 6 mm || power circuit 1.9-2.5 N.m Philips No 2 6 mm || power circuit 1.9-2.5 N.m pozidriv No 2 6 mm |
| Safe Separation Of Circuit | 400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 appendix N |
| Depth | 126 mm |
| Heat Dissipation | 3-3 W control circuit with LUCA, LUCB, LUCC, LUCD || 1.8-1.8 W control circuit with LUCM |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews




