LP2K1210BD
Schneider Electric
Reversing contactor, TeSys K, 3P, AC-3, lt or eq to 440V 12 A, 1 NO, 24VDC coil
AVAILABLE
GET A QUOTE NOW
- "LP2K1210BD is a compact 3-pole TeSys K reversing contactor from Schneider Electric for motor applications. Rated 12A AC-3 5.5kW@400V, it includes a 24V DC coil, 1NO auxiliary contact, a mechanical interlock and a pre-wired reversing circuit. LP2K1210BD is a 3-pole TeSys K reversing contactor from Schneider Electric for simple motor applications rated up to 5.5kW@400V. Very compact, DIN-rail compatible, it is assembled with a mechanical interlock and a pre-wired reversing circuit. It can be easily integrated into all control systems thanks to its 24V DC coil and 1NO built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Ready for connection to all control systems thanks to a 24V DC control voltage and 2NO built-in auxiliary contact. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K)."
| Specification | Value |
|---|---|
| Minimum Switching Current | 5 mA for signalling circuit |
| Control Circuit Voltage Limits | operational: 0.8...1.15 Uc (at <50 °C) || drop-out: 0.1...0.75 Uc (at <50 °C) |
| Non Overlap Distance | 0.5 mm |
| Hold-In Power Consumption In W | 3-3 W 20 °C |
| Insulation Resistance | > 10 MOhm for signalling circuit |
| Minimum Switching Voltage | 17 V for signalling circuit |
| Inrush Power In W | 3-3 W 20 °C) |
| Auxiliary Contacts Type | instantaneous 1 NO |
| Heat Dissipation | 3-3 W |
| Product Certifications | CB Scheme || CCC || UL || CSA || EAC || CE || UKCA |
| Interlocking Type | mechanical |
| [Uc] Control Circuit Voltage | 24 V DC |
| [Ue] Rated Operational Voltage | power circuit 690 V AC 50/60 Hz || signalling circuit <= 690 V AC 50/60 Hz |
| Average Impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| Auxiliary Contact Composition | 1 NO |
| [Ith] Conventional Free Air Thermal Current | 20 A (at 60 °C) for power circuit || 10 A (at 50 °C) for signalling circuit |
| Standards | EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 |
| Mounting Support | rail || plate |
| Control Circuit Type | DC standard |
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Contactor Application | motor control || resistive load |
| Rated Breaking Capacity | 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947 |
| Product Or Component Type | reversing contactor |
| Irms Rated Making Capacity | 144 A AC for power circuit conforming to IEC 60947 || 110 A AC for signalling circuit conforming to IEC 60947 |
| Product Name | TeSys K |
| Associated Fuse Rating | 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for signalling circuit conforming to IEC 60947 || 10 A gG for signalling circuit conforming to VDE 0660 |
| [Uimp] Rated Impulse Withstand Voltage | 8 kV |
| Connections - Terminals | screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.34-1.5 mm²flexible with cable end |
| Range | TeSys |
| Pole Contact Composition | 3 NO |
| Device Presentation | preassembled with reversing power busbar |
| Utilisation Category | AC-3 || AC-3e || AC-4 || AC-1 |
| [Ie] Rated Operational Current | 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit |
| Maximum Operating Rate | 3600 cyc/h |
| Electrical Durability | 1.3 Mcycles 12 A AC-3 <= 440 V || 1.3 Mcycles 12 A AC-3e <= 440 V || 0.3 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 72 A AC-4 <= 440 V |
| Mechanical Durability | 5 Mcycles |
| Poles Description | 3P |
| Operating Time | 30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening |
| Tightening Torque | 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2 |
| Overvoltage Category | III |
| Motor Power Kw | 3 kW 220...230 V AC 50/60 Hz || 5.5 kW 380...415 V AC 50/60 Hz || 5.5 kW 440 V AC 50/60 Hz || 4 kW 690 V AC 50/60 Hz |
| [Ui] Rated Insulation Voltage | power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-5-1 || signalling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || signalling circuit 600 V CSA C22.2 No 14 |
| Device Application | control |
| Device Short Name | LP2K |
| [Icw] Rated Short-Time Withstand Current | 115 A 50 °C - 1 s for power circuit || 105 A 50 °C - 5 s for power circuit || 100 A 50 °C - 10 s for power circuit || 75 A 50 °C - 30 s for power circuit || 55 A 50 °C - 1 min for power circuit || 50 A 50 °C - 3 min for power circuit || 25 A 50 °C - >= 15 min for power circuit || 80 A - 1 s for signalling circuit || 90 A - 500 ms for signalling circuit || 110 A - 100 ms for signalling circuit |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews