LC2D40AG7TQ

Schneider Electric

reversing contactor TeSys Deca - 3 poles - AC-3 - 440V 40A - coil 120V AC 60 Hz - TQPKG

AVAILABLE

GET A QUOTE NOW

  • "TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 40A/590V AC-3 (18.5kW@400V). It provides low consumption 100-250V AC/DC coils with electronic control, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), power connection by EverLink BTR screw connectors, control by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60\u00b0C, it procures high reliability and durability. Compact (119mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh)."
Read more arrow Read less arrow
Specification Value
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current 5 mA for signalling circuit
Control Circuit Voltage Limits 0.3...0.6 Uc -40-70 °C drop-out AC 60 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 60 Hz
Insulation Resistance > 10 MOhm for signalling circuit
Inrush Power In Va 160-160 VA 60 Hz 0.75 20 °C)
Coil Technology built-in bidirectional peak limiting diode suppressor
Minimum Switching Voltage 17 V for signalling circuit
Signalling Circuit Frequency 25...400 Hz
Heat Dissipation 4-5 W 60 Hz
Auxiliary Contacts Type mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va 13-13 VA 20 °C) 0.3 60 Hz
Interlocking Type mechanical
[Uc] Control Circuit Voltage 120 V AC 60 Hz
[Ue] Rated Operational Voltage power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Power Dissipation Per Pole 5.4 W AC-1 || 3.4 W AC-3
Average Impedance 1.5 mOhm - Ith 60 A 50 Hz for power circuit
Auxiliary Contact Composition 1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current 10 A (at 60 °C) for signalling circuit || 60 A (at 60 °C) for power circuit
Mounting Support plate || rail
Control Circuit Type AC 60 Hz
Standards CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application resistive load || motor control
Rated Breaking Capacity 800 A at 220/415/440 V for power circuit conforming to IEC 60947
Product Or Component Type reversing contactor
Product Certifications CCC || CSA || DNV || EAC || UKCA
Irms Rated Making Capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947-4
Product Name TeSys Deca
Associated Fuse Rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
Connections - Terminals control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 1-35 mm²flexible without cable end || power circuit screw clamp terminals 2 1-25 mm²flexible without cable end || power circuit screw clamp terminals 1 1-35 mm²flexible with cable end || power circuit screw clamp terminals 2 1-25 mm²flexible with cable end || power circuit screw clamp terminals 1 1-35 mm²solid without cable end || power circuit screw clamp terminals 2 1-25 mm²solid without cable end
Range TeSys || TeSys Deca
Pole Contact Composition 3 NO
Device Presentation preassembled with reversing power busbar
Utilisation Category AC-1 || AC-3
[Ie] Rated Operational Current 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Operating Time 4...19 ms opening || 12...26 ms closing
Maximum Operating Rate 3600 cyc/h 60 °C
Electrical Durability 1.5 Mcycles 40 A AC-3 <= 440 V || 1.4 Mcycles 60 A AC-1 <= 440 V
Tightening Torque control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm
Poles Description 3P
Overvoltage Category III
Motor Power Kw 18.5 kW at 380...400 V AC 50 Hz || 11 kW at 220...230 V AC 50 Hz || 22 kW at 415...440 V AC 50 Hz || 22 kW at 500 V AC 50 Hz || 30 kW at 660...690 V AC 50 Hz
Maximum Horse Power Rating 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 3 hp at 115 V AC 60 Hz for 1 phase motors || 30 hp at 575...600 V AC 60 Hz for 3 phase motors || 30 hp at 460...480 V AC 60 Hz for 3 phase motors || 5 hp at 230...240 V AC 60 Hz for 1 phase motors || 10 hp at 230...240 V AC 60 Hz for 3 phase motors
[Ui] Rated Insulation Voltage power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
Mechanical Durability 6000000 cycles
Device Short Name LC2D
[Icw] Rated Short-Time Withstand Current 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit || 320 A 40 °C - 10 s for power circuit || 720 A 40 °C - 1 s for power circuit || 72 A 40 °C - 10 min for power circuit || 165 A 40 °C - 1 min for power circuit
Protective Cover with
Read more arrow Read less arrow
*New items come with up to 24 month Obso Warranty
Our previously used items and repair options come with 12 months Obso Warranty.


"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
*Same & Next Day Delivery & Collection is available for stock from our UK and NL branches. Next-day delivery collection and 2 day delivery is available for stock sourced from our partners. In 90% of cases, we can deliver faster than the manufacturer’s ETA where required.

Standard options for delivery are also available where required.


"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
We are ISO 9001 accredited so you have peace of mind with your purchase.

What our customers say about us

Trustpilot

1

Step 1

    Part added for enquiry

    2

    Step 2

    Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.

    3

    Step 3

    We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.

    4

    Step 4

    Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.