LC1D65008P7
IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 2 NO and 2 NC, 230VAC 50/60Hz coil, open style
AVAILABLE
GET A QUOTE NOW
| Specification | Value |
|---|---|
| Power Dissipation Per Pole | 9.6 W AC-1 |
| Average Impedance | 1.5 mOhm - Ith 80 A 50 Hz for power circuit |
| [Ith] Conventional Free Air Thermal Current | 80 A (at 60 °C) for power circuit |
| Control Circuit Voltage Limits | 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz |
| Mounting Support | rail || plate |
| Contact Compatibility | M1 |
| Control Circuit Type | AC 50/60 Hz |
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Pollution Degree | 3 |
| Rated Breaking Capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
| Irms Rated Making Capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
| Associated Fuse Rating | 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit |
| Inrush Power In Va | 140-140 VA 60 Hz cos phi 0.75 (at 20 °C) || 160-160 VA 50 Hz cos phi 0.75 (at 20 °C) |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947 |
| Pole Contact Composition | 2 NO + 2 NC |
| Connections - Terminals | control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: solid without cable end |
| Coil Technology | without built-in suppressor module |
| Operating Time | 4...19 ms opening || 12...26 ms closing |
| Maximum Operating Rate | 3600 cyc/h 60 °C |
| Tightening Torque | control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || power circuit 5 N.m screw clamp terminals 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 |
| Electrical Durability | 1.4 Mcycles 80 A AC-1 <= 440 V |
| Mechanical Durability | 6 Mcycles |
| Compatibility Code | LC1D |
| Hold-In Power Consumption In Va | 13-13 VA 60 Hz cos phi 0.3 (at 20 °C) || 15-15 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Overvoltage Category | III |
| [Ui] Rated Insulation Voltage | power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1 |
| [Icw] Rated Short-Time Withstand Current | 640 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit || 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit |
| Heat Dissipation | 4-5 W at 50/60 Hz |
| Protective Cover | without |
| [Uc] Control Circuit Voltage | 230 V AC 50/60 Hz |
| [Ue] Rated Operational Voltage | power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC |
| Range Of Product | TeSys Deca |
| Contactor Application | resistive load |
| Product Or Component Type | contactor |
| Range | TeSys |
| Utilisation Category | AC-1 |
| [Ie] Rated Operational Current | 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
| Poles Description | 4P |
| Device Short Name | LC1D |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews





