ATV320U07M2C
variable speed drive, Altivar Machine ATV320, 0.75kW, 200 to 240V, 1 phase, compact
AVAILABLE
GET A QUOTE NOW
| Specification | Value |
|---|---|
| Variant | standard version |
| Format Of The Drive | compact |
| Product Or Component Type | variable speed drive |
| Ip Degree Of Protection | IP20 |
| Communication Port Protocol | Modbus serial || CANopen |
| Nominal Output Current | 4.8 A |
| Product Specific Application | complex machines |
| Option Card | communication module, CANopen || communication module, EtherCAT || communication module, Profibus DP V1 || communication module, PROFINET || communication module, Ethernet Powerlink || communication module, EtherNet/IP || communication module, DeviceNet |
| Range Of Product | Altivar Machine ATV320 |
| Motor Power Kw | 0.75 kW heavy duty |
| [Us] Rated Supply Voltage | 200...240 V - 15...10 % |
| Mounting Mode | wall mount |
| Emc Filter | Class C2 EMC filter integrated |
| Prospective Line Isc | 1 kA |
| Network Frequency | 50-60 Hz |
| Power Dissipation In W | self-cooled 45.0 W 200 V 4 kHz |
| Line Current | 10.1 A 200 V heavy duty) || 8.4 A 240 V heavy duty) |
| Analogue Output Type | software-configurable current AQ1 0...20 mA 800 Ohm 10 bits || software-configurable voltage AQ1 0...10 V DC 470 Ohm 10 bits |
| Discrete Output Type | open collector DQ+ 0-1 kHz 30 V DC 100 mA || open collector DQ- 0-1 kHz 30 V DC 100 mA |
| Asynchronous Motor Control Profile | voltage/frequency ratio, 5 points || flux vector control without sensor, standard || voltage/frequency ratio - Energy Saving, quadratic U/f || flux vector control without sensor - Energy Saving || voltage/frequency ratio, 2 points |
| Maximum Switching Current | relay output R1A, R1B, R1C resistive, cos phi = 1 3 A 250 V AC || relay output R1A, R1B, R1C resistive, cos phi = 1 3 A 30 V DC || relay output R1A, R1B, R1C, R2A, R2C inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1A, R1B, R1C, R2A, R2C inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2A, R2C resistive, cos phi = 1 5 A 250 V AC || relay output R2A, R2C resistive, cos phi = 1 5 A 30 V DC |
| 4 Quadrant Operation Possible | true |
| Relative Symmetric Network Frequency Tolerance | 5 % |
| Apparent Power | 2.0 kVA 240 V heavy duty) |
| Net Weight | 1.1 kg |
| With Safety Function Safe Direction (Sdi) | false |
| Relay Output Type | configurable relay logic R1A 1 NO 100000 cycles || configurable relay logic R1B 1 NC 100000 cycles || configurable relay logic R1C || configurable relay logic R2A 1 NO 100000 cycles || configurable relay logic R2C |
| Switching Frequency | 2...16 kHz adjustable || 4...16 kHz with derating factor |
| Analogue Input Number | 3 |
| Motor Slip Compensation | automatic whatever the load || adjustable 0...300 % || not available in voltage/frequency ratio (2 or 5 points) |
| Discrete Output Number | 3 |
| With Safety Function Safe Position (Sp) | false |
| Method Of Access | slave CANopen |
| With Safety Function Safely Limited Position (Slp) | false |
| With Safety Function Safe Operating Stop (Sos) | false |
| Discrete Input Number | 7 |
| With Sft Fct Safe Stop 2 (Ss2) | false |
| With Safety Function Safe Stop 1 (Ss1) | true |
| Width | 72.0 mm |
| Depth | 138.0 mm |
| Analogue Input Type | AI1 voltage 0...10 V DC 30 kOhm 10 bits || AI2 bipolar differential voltage +/- 10 V DC 30 kOhm 10 bits || AI3 current 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration) 250 Ohm 10 bits |
| Maximum Output Frequency | 0.599 kHz |
| With Safety Function Safe Brake Management (Sbc/Sbt) | false |
| Height | 143.0 mm |
| Acceleration And Deceleration Ramps | linear || U || S || CUS || ramp switching || acceleration/deceleration ramp adaptation || acceleration/deceleration automatic stop with DC injection |
| Maximum Output Voltage | 240 V |
| Base Load Current At High Overload | 33.0 A |
| With Safety Function Safe Speed Monitor (Ssm) | false |
| Transient Overtorque | 170-200 % of nominal motor torque |
| With Safety Function Safe Torque Off (Sto) | true |
| Analogue Output Number | 1 |
| Minimum Switching Current | relay output R1A, R1B, R1C, R2A, R2C 5 mA 24 V DC |
| Discrete Input Logic | positive logic (source) || negative logic (sink) |
| With Safety Function Safe Programmable Logic | false |
| Brake Chopper Integrated | true |
| Nominal Switching Frequency | 4 kHz |
| Braking To Standstill | by DC injection |
| Discrete Input Type | STO safe torque off, 24 V DC1.5 kOhm || DI1...DI6 logic inputs, 24 V DC 30 V) || DI5 programmable as pulse input 0-30 kHz, 24 V DC 30 V) |
| Protection Type | input phase breaks drive || overcurrent between output phases and earth drive || overheating protection drive || short-circuit between motor phases drive || thermal protection drive |
| With Safety Function Safely Limited Speed (Sls) | true |
| Synchronous Motor Control Profile | vector control without sensor |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews