TPRST025

Schneider Electric

Motor starter, TeSys island, 30A at AC-1, 25A at AC-3, 11kW, 15hp, DOL type

Dostępny

Uzyskaj wycenę już teraz

  • "TeSys island direct starter, 3 poles, 25A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 25A and motors up to 11kW@400V / 15hp@480V. It provides motor protection functions including thermal overload (setting 0.5-25A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh)."
Więcej informacji arrow Czytaj mniej arrow
Specification Value
Mounting Mode horizontal and vertical 35 mm symmetrical DIN rail)
Height 121 mm
Product Certifications CCC || UL || CSA || EAC
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Standards EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Connections - Terminals screw-clamp terminals 1 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 2 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 1 2.5-10 mm² AWG 14...AWG 8)flexible without cable end || screw-clamp terminals 2 2.5-10 mm² AWG 14...AWG 8)flexible without cable end || screw-clamp terminals 1 1.5-10 mm² AWG 16...AWG 10)flexible with cable end || screw-clamp terminals 2 1.5-6 mm² AWG 16...AWG 10)flexible with cable end
Net Weight 0.718 kg
Metering Type time device ON || time device switch ON || number of faults || number of switching cycles || number of device power cycles || average current Iavg || average voltage Vavg || max current Imax || max voltage Vmax || active and reactive power with voltage module || active and reactive energy with voltage module || true power factor with voltage module
Maximum Operating Rate 3600 cyc/mn AC-3
Local Signalling for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red)
Electrical Durability 1.65 Mcycles 25 A AC-3 440 V || 2 Mcycles 30 A AC-1 440 V
Mechanical Durability 30 Mcycles
Operating Time < 100 ms closing || < 30 ms opening
Width 45 mm
Depth 115 mm
Tightening Torque 2.5-2.5 N.m flat Ø 6 mm || 2.5-2.5 N.m Philips No 3
Protection Type thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || rapid restart lockout || phase sequence || phase reversal || phase loss || phase unbalance || ground current
Current Consumption 160 mA contactor sealed || 160 mA contactor closing
Power Dissipation In W 6.6 W at Ie AC-3
Power Dissipation Per Pole 1.25 W AC-3 - Ith 25 A || 1.8 W AC-1 - Ith 30 A
Average Impedance 2 mOhm - Ith 30 A 50 Hz
Reset remotely or automatically
[Ith] Conventional Free Air Thermal Current 30 A (at 50 °C)
[Uc] Control Circuit Voltage 24 V DC supplied by the bus coupler
Rated Breaking Capacity 450 A at 440 V conforming to IEC 60947
Product Or Component Type motor starter
Irms Rated Making Capacity 450 A at 440 V conforming to IEC 60947
Product Name TeSys island
Thermal Overload Class class 5…30
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947-1
Range TeSys
Device Presentation direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
Motor Starter Type direct on line
Utilisation Category AC-1 || AC-2 || AC-3 || AC-4
Function Available upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module
[Ie] Rated Operational Current 25 A (at <50 °C) at <= 440 V AC-3 || 30 A (at <50 °C) at <= 440 V AC-1
Overvoltage Category III for Ue <= 480 V || II for Ue <= 690 V
Thermal Protection Adjustment Range 0.5-25 A
Product Compatibility TPRBC bus coupler || TPRVM voltage interface module
[Ue] Rated Operational Voltage <= 480 V AC 47...63 Hz for overvoltage cat. III || <= 690 V AC 47...63 Hz for overvoltage cat. II
Maximum Horse Power Rating 2 hp at 120 V AC 60 Hz for 1 phase motors || 3 hp at 240 V AC 60 Hz for 1 phase motors || 7.5 hp at 208 V AC 60 Hz for 3 phase motors || 7.5 hp at 240 V AC 60 Hz for 3 phase motors || 15 hp at 480 V AC 60 Hz for 3 phase motors || 20 hp at 600 V AC 60 Hz for 3 phase motors
Motor Power Kw 5.5 kW at 230 V 50 Hz (AC-3) || 11 kW at 380...415 V 50 Hz (AC-3) || 11 kW at 440 V 50 Hz (AC-3) || 15 kW at 500 V 50 Hz (AC-3) || 15 kW at 690 V 50 Hz (AC-3)
[Ui] Rated Insulation Voltage 690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Device Short Name TPRST
Poles Description 3P 3 NO
[Icw] Rated Short-Time Withstand Current 380 A 40 °C - 1 s || 240 A 40 °C - 10 s || 120 A 40 °C - 1 min || 50 A 40 °C - 10 min
Więcej informacji arrow Czytaj mniej arrow
*Nowe produkty są objęte 24-miesięczną gwarancją Obso.
Nasze wcześniej używane produkty i opcje naprawy są objęte 12-miesięczną gwarancją Obso.


„Super obsługa! Wszystko zostało przetworzone bardzo szybko i kompetentnie, a osobiste wsparcie było doskonałe. Zawsze ponownie wybrałbym Obso Automation! Wielkie dzięki za świetne wsparcie.” - MJ
*Dostawa i odbiór tego samego i następnego dnia są dostępne dla towarów z naszych oddziałów w Wielkiej Brytanii i Holandii. Odbiór następnego dnia i dostawa w ciągu 2 dni są dostępne dla towarów pochodzących od naszych partnerów. W 90% przypadków możemy dostarczyć towar szybciej niż przewidywany czas dostawy producenta.

W razie potrzeby dostępne są również standardowe opcje dostawy.


„Profesjonalny, uprzejmy i dokładny. Przestarzała część wyceniona tego samego dnia i dostarczona następnego” - PT
Posiadamy akredytację ISO 9001, dzięki czemu możesz być spokojny o swój zakup.

Co mówią o nas nasi klienci

Trustpilot

1

Step 1

    Część dodana do zapytania

    2

    Krok 2

    Twój osobisty opiekun klienta już się tym zajmuje, zapewniając szybką reakcję i bezkonkurencyjną obsługę.

    3

    Krok 3

    Nie tylko przetwarzamy zamówienia – gwarantujemy sprawną dostawę, pełną przejrzystość i zero bólu głowy.

    4

    Krok 4

    Nie bez powodu zaufało nam ponad 10 000 klientów. Uzyskaj wycenę już teraz i doświadcz automatyzacji bez ryzyka, opóźnień i niepewności.