LU2B32BL

Schneider Electric

Reversing power base, TeSys Ultra, 3P, 32A/690V, coil 24VDC

Disponible

Obtenez un devis maintenant

  • "TeSys U standard reversing power base, 3 poles (3NO), rated 32A/690V, to be completed with a control unit LUC to form a TeSys U reversing starter controller, for 3-phase motor applications up to 15kW@400V. Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a \"all in one\" reversing starter controller with basic or advanced protection and control functions. It is equipped with a reverser module LU2MB0BL to be supplied with 24V DC, auxiliary signaling contacts (1NO+1NC), a control terminal block, blanking shutters covering the empty cavities. It provides a high breaking capacity Icu 50kA@400V, start-stop control guaranteed for 3600 cycles/hour. Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle. Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh)."
Plus d'informations arrow Lire moins arrow
Specification Value
Product Certifications CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
Height 224 mm
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Maximum Operating Rate 3600 cyc/h
Connections - Terminals control circuit screw clamp terminals 1 0.34-1.5 mm² flexible with cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² flexible without cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² rigid || control circuit screw clamp terminals 2 0.34-1.5 mm² flexible with cable end || control circuit screw clamp terminals 2 0.75-1.5 mm² flexible without cable end || control circuit screw clamp terminals 2 0.75-1.5 mm² rigid || power circuit screw clamp terminals 1 1-10 mm² rigid || power circuit screw clamp terminals 1 1-6 mm² flexible with cable end || power circuit screw clamp terminals 1 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 2 1-6 mm² flexible with cable end || power circuit screw clamp terminals 2 1-6 mm² rigid || power circuit screw clamp terminals 2 1.5-6 mm² flexible without cable end
Net Weight 1.27 kg
Fixing Mode clipped DIN rail) || screw-fixed plate)
[Uimp] Rated Impulse Withstand Voltage 6 kVIEC 60947-6-2
Inrush Restraint Duration 15 ms DC
Standards EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier
[Ui] Rated Insulation Voltage 690 V IEC 60947-6-2 3) || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Typical Current Consumption 120 mA 24 V DC I maximum while closing || 120 mA 24 V DC I rms sealed
Mechanical Durability 15 Mcycles
Compatibility Code LU2B
Operating Time 150 ms with change of direction power circuit || 75 ms without change of direction power circuit || 35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM control circuit || 75 ms closing with LUCM control circuit || 70 ms closing with LUCA, LUCB, LUCC, LUCD control circuit
Width 45 mm
Tightening Torque control circuit 0.8-1.2 N.m flat 5 mm || control circuit 0.8-1.2 N.m Philips no 1 5 mm || power circuit 1.9-2.5 N.m flat 6 mm || power circuit 1.9-2.5 N.m Philips No 2 6 mm || power circuit 1.9-2.5 N.m pozidriv No 2 6 mm
Safe Separation Of Circuit 400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 appendix N
Depth 126 mm
Heat Dissipation 3-3 W control circuit with LUCA, LUCB, LUCC, LUCD || 1.8-1.8 W control circuit with LUCM
[Ics] Rated Service Breaking Capacity 50 kA 230 V || 50 kA 440 V || 10 kA 500 V || 4 kA 690 V
[Ue] Rated Operational Voltage 690 V AC power circuit
Auxiliary Contact Composition 1 NO + 1 NC
[Uc] Control Circuit Voltage 24 V DC
Product Or Component Type reversing power base
[Ith] Conventional Free Air Thermal Current 32 A
Product Name TeSys Ultra
Range TeSys
Utilisation Category AC-43 || AC-44 || AC-41
[Ie] Rated Operational Current 28.5 A <= 440 V || 23 A 500 V || 21 A 690 V
Suitability For Isolation yes
Product Compatibility control unit LUC.X6BL || control unit LUC.1XBL || control unit LUC.05BL || control unit LUC.12BL || control unit LUC.18BL || control unit LUC.32BL
Auxiliary Contacts Type linked contacts 1 NO + 1 NC) IEC 60947-4-1 || mirror contact 1 NC) IEC 60947-1
Poles Description 3P
Control Circuit Voltage Limits 14.5 V DC drop-out || 20...27 V DC in operation
Network Frequency 40...60 Hz
Device Application motor control || motor protection
Device Short Name LU2B
Plus d'informations arrow Lire moins arrow
*Les articles neufs bénéficient d'une garantie Obso de 24 mois.
Nos articles d'occasion et nos options de réparation sont assortis d'une garantie Obso de 12 mois.


"Super service ! Tout a été traité très rapidement et avec compétence et l'assistance personnelle était excellente. Je choisirai toujours Obso Automation ! Merci beaucoup pour votre soutien." - MJ
*La livraison et l'enlèvement le jour même et le jour suivant sont disponibles pour les stocks de nos succursales au Royaume-Uni et aux Pays-Bas. La livraison et l'enlèvement le jour suivant et la livraison en deux jours sont disponibles pour les stocks provenant de nos partenaires. Dans 90% des cas, nous pouvons livrer plus rapidement que l'ETA du fabricant si nécessaire.

Des options de livraison standard sont également disponibles si nécessaire.


"Professionnel, courtois et précis. La pièce obsolète a fait l'objet d'un devis le jour même et a été livrée le lendemain" - PT
Nous sommes accrédités ISO 9001, ce qui vous permet d'acheter en toute tranquillité.

Qu'est-ce que nos clients disent de nous

Trustpilot

1

Step 1

    Partie ajoutée pour enquête

    2

    Étape 2

    Votre gestionnaire de compte personnel est déjà sur le coup et vous fournit des réponses rapides avec un service imbattable.

    3

    Étape 3

    Nous ne nous contentons pas de traiter les commandes, nous garantissons une livraison sans heurts, une transparence totale et une absence totale de maux de tête.

    4

    Étape 4

    Plus de 10 000 clients nous font confiance pour une bonne raison. Obtenez votre devis dès maintenant et découvrez l’automatisation sans risque, ni délai, ni incertitude.