- "TeSys GB circuit breaker, 2 poles (2P), 2A/415V, for the protection of industrial equipment control circuits. It provides thermal magnetic protection with a magnetic tripping level at 26A (13 In) and breaking capacity Icu 15kA@415V. It can also be used for protection of DC loads up to 2A/48V DC-13 with a breaking capacity Icu 1.5kA@24V. Compact device (30mm wide), mounting on 35mm DIN-rail, control by toggle lever (start-stop guaranteed for 8000 cycles). Sold in lots of 3 units. It conforms to IEC 60947-1 and IEC 60947-2, Green Premium product (RoHS/REACh)."
| Specification | Value |
|---|---|
| Mechanical Robustness | shocks 22 Gn for 20 ms IEC 60068-2-27 || vibrations 5 Gn, 5...110 Hz IEC 60068-2-6 |
| Line Rated Current | 2 A |
| [Ue] Rated Operational Voltage | 415 V AC 50/60 Hz IEC 60947-2 || 48 V DC |
| Height | 74 mm |
| Mounting Support | rail || plate |
| 9 Mm Pitches | 4 |
| Net Weight | 0.115 kg |
| Connections - Terminals | connector 1 0.75-6 mm²solid without cable end || connector 2 0.75-4 mm²solid without cable end || connector 1 0.75-4 mm²flexible with cable end || connector 2 0.75-2.5 mm²flexible with cable end |
| [Uimp] Rated Impulse Withstand Voltage | 4 kV IEC 60947-2 |
| Control Type | toggle |
| Power Dissipation Per Pole | 2 W |
| Electrical Durability | 8000 cycles |
| Mounting Mode | by clips |
| Tightening Torque | 1.2 N.m connector |
| Mechanical Durability | 8000 cycles |
| Quantity Per Set | set of 3 |
| Mounting Position | vertical || horizontal |
| Width | 30 mm |
| Depth | 70 mm |
| Network Type | AC/DC |
| Magnetic Tripping Current | 26-26 A |
| Product Or Component Type | circuit breaker |
| Product Name | TeSys GB2 |
| Utilisation Category | category A IEC 60947-2 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 |
| Range | TeSys |
| [Ics] Rated Service Short-Circuit Breaking Capacity | 25 % 230/240 V AC 50/60 Hz IEC 60947-2 || 50 % 110 V AC 50/60 Hz IEC 60947-2 || 25 % 400/415 V AC 50/60 Hz IEC 60947-2 |
| Breaking Capacity | 15 kA Icu 110 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 24 V DC IEC 60947-2 || 1 kA Icu 48 V DC IEC 60947-2 |
| Poles Description | 2P |
| Network Frequency | 50/60 Hz IEC 60947-2 |
| Device Application | control |
| Device Short Name | GB2 |
| Trip Unit Technology | thermal-magnetic |
Nos articles d'occasion et nos options de réparation sont assortis d'une garantie Obso de 12 mois.
"Super service ! Tout a été traité très rapidement et avec compétence et l'assistance personnelle était excellente. Je choisirai toujours Obso Automation ! Merci beaucoup pour votre soutien." - MJ
Des options de livraison standard sont également disponibles si nécessaire.
"Professionnel, courtois et précis. La pièce obsolète a fait l'objet d'un devis le jour même et a été livrée le lendemain" - PT
1
Step 1
Partie ajoutée pour enquête
2
Étape 2
Votre gestionnaire de compte personnel est déjà sur le coup et vous fournit des réponses rapides avec un service imbattable.
3
Étape 3
Nous ne nous contentons pas de traiter les commandes, nous garantissons une livraison sans heurts, une transparence totale et une absence totale de maux de tête.
4
Étape 4
Plus de 10 000 clients nous font confiance pour une bonne raison. Obtenez votre devis dès maintenant et découvrez l’automatisation sans risque, ni délai, ni incertitude.
Google Reviews