LTMEV40FM
Extension module, TeSys T, 4 inputs, 100 to 240VAC, for LTMR controller
AVAILABLE
GET A QUOTE NOW
| Specification | Value |
|---|---|
| Contacts Type And Composition | without |
| Height | 61 mm |
| Connection Pitch | 5.08 mm |
| Pollution Degree | 3 |
| Logic Input Number | 4 |
| Maximum Operating Rate | 1800 cyc/h |
| Connections - Terminals | control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)solid without cable end |
| Input Current | 3.1 mA 100 V || 7.5 mA 240 V |
| Current State 1 Guaranteed | logic input 79...264 V <= 15 mA 25 ms |
| Net Weight | 0.21 kg |
| [Uimp] Rated Impulse Withstand Voltage | 4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 |
| Electromagnetic Compatibility | electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || voltage inputs: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || voltage inputs: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 |
| Measurement Accuracy | 1 % voltage 100...830 V) || 3 % power factor || 5 % active and reactive power |
| Current State 0 Guaranteed | logic input 0...40 V 2...15 mA 25 ms |
| [Ui] Rated Insulation Voltage | 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508 |
| Compatibility Code | LTME |
| Width | 45 mm |
| Tightening Torque | control circuit 0.5-0.6 N.m flat 3 mm |
| Overvoltage Category | III |
| Depth | 120.7 mm |
| Maximum Operating Frequency | 2 Hz |
| Metering Type | imbalance voltage || active power P, P1, P2, P3 || calculated active and reactive energy (+/- W.h, +/- VAR.h) || voltage U21, U32, U13, V1, V2, V3 || reactive power Q, Q1, Q2, Q3 || frequency || power factor |
| Range Compatibility | TeSys TeSys T LTMR motor controller |
| Supply | via the controller |
| Product Or Component Type | extension module |
| Product Name | TeSys T |
| Range | TeSys |
| Device Application | equipment monitoring and control |
| Device Short Name | LTME |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews