M9R11240
Schneider Electric
Residual current circuit breaker (RCCB), Multi9 ID, 2P, 40A, AC type, 30mA
AVAILABLE
GET A QUOTE NOW
- "This product is a Multi ID residual current circuit breaker (RCCB). It is a 2P circuit breaker with 40A In rated current, a sensitivity of 30mA with a AC type protection class. This product protects against electrical shock by direct or indirect contact and fire hazards. The tripping upon fault is indicated by a red mechanical status indicator on the front panel. This product is dedicated to original equipment manufacturers (OEM) and control panel builders in indisutrial and tertiary buildings. It is compliant with IEC/EN 61008-1 standard. The (Im/I\u0394m) rated breaking and making short circuit capacity is 400A. The (Inc/I\u0394c) conditional rated short circuit current is 10kA. The mechanical endurance is going up to 20000 cycles and electrical endurance going up to 2000 cycles. The Ue operational voltage is 220VAC to 240VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 6kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 73mm. The weight is 0.23kg. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -5\u00b0C to 40\u00b0C. The storage temperature is from -40\u00b0C to 60\u00b0C."
| Specification | Value |
|---|---|
| Network Frequency | 50 Hz |
| Height | 81 mm |
| Contact Position Indicator | yes |
| Locking Options Description | padlocking device |
| Mounting Support | DIN rail |
| 9 Mm Pitches | 4 |
| Surge Current | 250 A |
| Connections - Terminals | tunnel type terminal top or bottom) 1-35 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 3 16-16 mm² - rigid || tunnel type terminal top or bottom) 3 10-10 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule |
| Net Weight | 0.23 kg |
| Wire Stripping Length | 15 mm for top or bottom connection |
| Control Type | toggle |
| Residual Current Tripping Technology | voltage independent |
| [Ui] Rated Insulation Voltage | 440 V AC 50 Hz EN/IEC 61008-1 |
| Mounting Mode | clip-on |
| Electrical Durability | 2000 cycles |
| Rated Breaking And Making Capacity | Idm 400 A EN/IEC 61008-1 |
| Mechanical Durability | 20000 cycles |
| Local Signalling | ON, OFF, fault trip |
| [Uimp] Rated Impulse Withstand Voltage | 6 kVEN/IEC 61008-1 |
| Color | Gray |
| Width | 36 mm |
| Depth | 73 mm |
| Tightening Torque | 3.5-3.5 N.m top or bottom |
| Rated Conditional Short-Circuit Current | Inc 10 kA |
| [Ue] Rated Operational Voltage | 220...240 V AC 50 Hz |
| Line Rated Current | 40 A |
| Network Type | AC |
| Earth-Leakage Protection Class | type AC |
| Earth-Leakage Sensitivity | 30 mA |
| Product Or Component Type | residual current circuit breaker (RCCB) |
| Product Name | Multi9 ID |
| Range | Multi9 |
| Earth-Leakage Protection Time Delay | instantaneous |
| Poles Description | 2P |
| Neutral Position | left |
| Device Application | distribution |
| Device Short Name | ID |
Our previously used items and repair options come with 12 months Obso Warranty.
"Super service! Everything was processed very quickly and competently and the personal support was excellent. I would always choose Obso Automation again! Many thanks for the great support." - MJ
Standard options for delivery are also available where required.
"Professional, courteous and accurate. Obsolete part quoted same day and supplied next" - PT
1
Step 1
Part added for enquiry
2
Step 2
Your personal Account Manager is already on it, delivering rapid responses and unbeatable service.
3
Step 3
We don’t just process orders—we guarantee smooth delivery, full transparency, and zero headaches.
4
Step 4
Our 10,000+ customers trust us for a reason. Get your quote now and experience automation without risk, delays, or uncertainty.
Google Reviews